Wall-mounted oxygen sensor AERASGARD® AO2

Product group: WG02

Low availability.

Usually ships in 3 to 5 days
$ 1.887,51
$ 603.96 (special net price)
$ 718,71 incl. sales tax + shipping
+

Description

Wall-mounted oxygen sensor AERASGARD® AO2
The measuring device detects the oxygen content O2 (0-25%) in the ambient air. The transmitter converts the measured value into a standardized, analog output signal 0-10 V.


As an option, the measuring instrument has a backlit, rotatable display and potential-free changeover contact. The version with backlit LCD display shows the measured values and in/max values.
The measuring instrument performs an automatic calibration at regular intervals, which ensures a long-term stable measurement. This can also be performed manually on the instrument at any time.
The oxygen meter is optimally suited for use in workplaces, medical facilities, HVAC applications, greenhouses

Technical details

Warranty
12 months
Voltage supply
24 V DC (± 5%)
Power consumption
Ø 50mA (depending on backlight, + peak option relay)
Operating range, humidity
0...98% r.H., pollutant-free, non-precipitating air
Operating range, temperature
32...+122 °F
Warm up time
10 min
Response time
< 10s
Output
0 - 10V, 3-wire connection
Sensor
Electrochemical sensor
with manual calibration (via zero button) and
automatic calibration (fixed)

Sensor replacement recommended after 18 months
Manual calibration every 3 months, with automatic calibration switched off
Measuring range
0...25% O2
Accuracy
± 0,2% vol. + max. ±0,5% EW (@ 20°C, 45% r.H., 1013 mbar)
Operating temperature
+32...+122 °F
Storage temperature
-4...+122 °F
Electrical connection
AWG 16 - 26 via terminal screws

Housing
Polycarbonate with hinge locks
Color signal white (similar to RAL 9003)
Cable gland
M 16 x 1.5; including strain relief
Dimensions
90,9 x 80 x 48mm
Long-term stability
±1% EW/ Year
±0,2% EW/ Year with auto calibration ON
Protection class
III (according to EN 60 730)
Protection type
IP 65