- New
- Sale
- Temperature
- Humidity
- Pressure
- Light Intensity & Motion
- Air Quality
- Flow
- Modbus | Wireless Modbus
- Room controller
- EtherCAT P
- Accessory
Description
Room pendulum humidity and temperature sensor
HYGRASGARD® RPFF - 25/ RPFTF - 25
Calibratable HYGRASGARD® RPFF - 25 / RPFTF - 25 pendulum room humidity and temperature measuring transducer with pluggable metal sinter filter, housing made of impact resistant plastic, with/without optional display. The sensor device measures relative humidity and/or air temperature and converts the measurands into a standard signal of 0-10 V or 4...20 mA. It supports with four switchable temperature ranges.
The transmitter is applied in non-aggressive dust-free atmospheres in refrigeration, air conditioning, ventilation and cleanroom engineering, hotels, technical rooms, meeting rooms and convention centres. It provides precise detection of temperature and humidity. A digital long-term stable sensor is used as measuring element for humidity and temperature. The sensor is suitable for ceiling and duct installation, or for integration into equipment. It is factory-calibrated and can be fine-tuned to ambient conditions by an expert.
Technical details
Power consumption
< 1.1 VA/ 24 V DC ; < 2.2 VA/ 24 V AC
Operating range, humidity
0...95 % RH (without dew formation)
Sensor protection
pluggable measuring head (probe) with
metal sinter filter, Ø 0.63 in, L = 3.48 in, exchangeable
metal sinter filter, Ø 0.63 in, L = 3.48 in, exchangeable
Accuracy
typical ± 1,8 % RH (10…90 % RH ); at + 77 °F, otherwise ± 2 %
Ambient temperature
storage –31...+185 °F
operation –22...+158 °F
operation –22...+158 °F
Protective tube
stainless steel V2A (1.4301), Ø = 0.71 in (0.63 in), L = 4.72 in
Electrical connection
2-, 3- or 4-wire connection
AWG 26 - 16 via terminal screws on circuit board
AWG 26 - 16 via terminal screws on circuit board
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 0.4 in) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing dimensions
4.96 x 3.54 x 1,97 in (Tyr 2)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 0.4 in
max. inner diameter 0.4 in
sensor cable
KL = 6.5 ft
Long-term stability
± 1 % per year
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Standards
CE conformity,
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3