Description
Pendulum room humidity sensor
HYGRASGARD® RPFF-SD
The calibratable HYGRASGARD® RPFF - SD pendulum humidity transmitter with plastic sinter filter measures the relative humidity of the air. It converts the measurand into a standard signal of 4...20 mA. Relative humidity (in % r.H.) is the quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature.
The measuring transducer is used in non-aggressive, dust-free environments, in refrigeration, air conditioning and cleanroom engineering, hotels, engineering rooms, meeting and conference facilities. It provides precise detection of humidity. A digital long-term stable sensor is used as measuring element for humidity. The sensor is suitable for duct installation, as a pendulum sensor, or for integration in equipment.
Technical details
Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
depending on working resistance, residual ripple stabilised ± 0.3 V
Power consumption
< 1.1 VA/ 24 V DC
Working resistance
Ra (Ohm) = (Ub -14 V)/ 0.03 A
Ra < 500 Ohm
Ra < 500 Ohm
Measuring range, humidity
0...100 % RH
(output corresponding to 4...20 mA)
(output corresponding to 4...20 mA)
Operating range, humidity
0...95 % RH (without dew formation)
Output
4...20 mA
Sensor protection
plastic sinter filter, Ø 0.63 in, L = 1.38 in, exchangeable
(optional metal sinter filter, Ø 0.63 in, L = 1.26 in)
(optional metal sinter filter, Ø 0.63 in, L = 1.26 in)
Accuracy
typical ± 2 % RH (20…80 % RH ); at + 77 °F, otherwise ± 3 %
Ambient temperature
storage –13...+122 °F,
operation +23...+131 °F
operation +23...+131 °F
Protective tube
stainless steelV2A (1.4301), Ø = 0.63 in, L = 5.59 in
Electrical connection
2-wire Connection,
0.14 - 1.5 mm²
0.14 - 1.5 mm²
sensor cable
PVC, LiYY, 2 x 24 AWG,
KL = approx. 5 ft (other lengths optional)
KL = approx. 5 ft (other lengths optional)
Long-term stability
± 1 % per year
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Standards
CE conformity,
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3