- New
- Sale
- Temperature
- Humidity
- Pressure
- Light Intensity & Motion
- Air Quality
- Flow
- Modbus | Wireless Modbus
- Room controller
- EtherCAT P
- Accessory
Description
Pressure and differential pressure measuring transducers
PREMASGARD® 11D - Modbus
Maintenance-free microprocessor-controlled PREMASGARD® 11D7 - Modbus
with Modbus connection, in an impact-resistant plastic housing,
for measuring the differential pressure (max. –28...+28 inWC) in the air. Incl. connection set ASD-06 (2 m / 78.74 in connecting hose, two pressure
port nipples, screws).
The pressure sensor is applied to measure positive, negative or differential pressure in clean air and gaseous media. It is used in clean-room, medical
and filter technology, ventilation and air-conditioning ducts, spray booths, large-scale catering facilities, for filter monitoring and level measurement
or for triggering frequency converters.
for measuring the differential pressure (max. –28...+28 inWC) in the air. Incl. connection set ASD-06 (2 m / 78.74 in connecting hose, two pressure
port nipples, screws).
The pressure sensor is applied to measure positive, negative or differential pressure in clean air and gaseous media. It is used in clean-room, medical
and filter technology, ventilation and air-conditioning ducts, spray booths, large-scale catering facilities, for filter monitoring and level measurement
or for triggering frequency converters.
Innovative
Modbus sensor with galvanically separated RS485 Modbus interface,
selectable bus termination resistance, DIP switch for setting the
bus parameters and bus address in current-free state, LEDs for telegram status display and one a push-in terminal. The sensor is factory-calibrated;
an environmental precision adjustment by an expert is possible.
bus parameters and bus address in current-free state, LEDs for telegram status display and one a push-in terminal. The sensor is factory-calibrated;
an environmental precision adjustment by an expert is possible.
Technical details
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
15…36 V DC
Power consumption
< 0.8 W/ 24 V DC typically; < 1.0 VA/ 24 V AC typically
Data points
Differential pressure [Pa],
volume flow [m3/h]
volume flow [m3/h]
Pressure range
±28 inWC
Media temperature
–4...+122 °F (temperature-compensated +32...+122 °F)
Pressure connection
with connection nozzles for pressure hose Ø 0.24 in
Type of pressure
differential pressure
Zero point offset
± 10 % measuring range
Above- below-pressure
max. ± 201 inWC
Ambient temperature
-22...+158 °F
Medium
clean air and
non-aggressive, non-combustible gases
non-aggressive, non-combustible gases
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
address range 0...247 selectable
Signal filtering
0 s / 1 s / 10 s
Electrical connection
AWG 24 - 16, via push-in terminal
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe-reinforced,
colour traffic white (similar to RAL 9016)
material polyamide, 30 % glass-globe-reinforced,
colour traffic white (similar to RAL 9016)
Housing dimensions
4.25 x 2.76 x 2.89 in (Thor 2)
Cable gland
M 20 x 1.5; including strain relief
Long-term stability
± 1 % per year
Hysteresis
0.3 % of final value
Media contacting parts
Brass, Ni, Duroplast, Si, epoxy, RTV, BSG, UV silicone gel
Temperature drift values
± 0.1 %/ K
Linearity
< ± 1 % of final value
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) enclosure only!
Protection type housing
IP 65
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU