- New
- Sale
- Temperature
- Humidity
- Pressure
- Light Intensity & Motion
- Air Quality
- Flow
- Modbus | Wireless Modbus
- Room controller
- EtherCAT P
- Accessory
Description
Dual pressure sensor as pressure transmitter and differential pressure transmitter
PREMASGARD® 724x - Modbus
Maintenance-free, microprocessor-controlled PREMASGARD® 724x - Modbus
(series) with Modbus connection, in an impact-resistant plastic housing
with quick-locking screws, connection nozzles for pressure hose (Ø 0.24 in), with cable gland or M12 connector according to DIN EN 61076-2-101,
optionally with/without display, for measuring the differential pressure
(2 measuring channels, max. ± 28.1 inWC) in air. Type variant 724x T with connection facility for external Pt1000
sensor (sensor element not included in the scope of delivery) for
detecting the temperature (–58...+302°F). International system of units SI (default) can be switched to Imperial (via Modbus). Incl. connection set ASD-06 (2 m connecting hose, two pressure port nipples, screws).
The pressure sensor is applied to measure positive, negative or
differential pressure in clean air and gaseous media. It is used in the
clean room, medical and filter technology, ventilation and air
conditioning ducts, spray booths, large-scale catering facilities, for
filter monitoring and level measurement or for triggering frequency
converters. A pressure sensor with piezoresistive measuring
element guarantees exact measurement results. The following measured
values can be accessed via the Modbus: Differential pressure, volume
flow and temperature.
Innovative Modbus sensor with galvanically separated RS485 Modbus interface, selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal LEDs for telegram status display, two separate push-in terminals and large threeline display (illuminated; with customised programming in the 7-segment and dot-matrix range). The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
Innovative Modbus sensor with galvanically separated RS485 Modbus interface, selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal LEDs for telegram status display, two separate push-in terminals and large threeline display (illuminated; with customised programming in the 7-segment and dot-matrix range). The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
Technical details
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
15…36 V DC
Power consumption
< 4.8 W/ 24 V DC typical; < 6.8 VA/ 24 V AC typical
Data points
Temperature, differential pressure
Measuring range, temperature
-58...+302°F
Operating range, temperature
typically ± 0.4 °F at +77 °F
Sensor protection
plastic sinter filter, Ø 0.63 in, L = 1.38 in, exchangeable
(optional metal sinter filter, Ø 0.63 in, L = 1.26 in)
(optional metal sinter filter, Ø 0.63 in, L = 1.26 in)
Media temperature
-4...+122 °F
Pressure connection
with connection nozzles for pressure hose Ø 0.24 in
Type of pressure
differential pressure
Accuracy
Type 7249 (2.0 inWC): typically ± 0.05 inWC compared to calibrated reference device
Type 724x (28 inWC): typical ± 0.42 inWC compared to a calibrated reference device
Type 724x (28 inWC): typical ± 0.42 inWC compared to a calibrated reference device
Zero point offset
< ± 0.7 % of final value
Above- below-pressure
max. ± 201 inWC
Ambient temperature
-22...+158 °F
Medium
clean air and
non-aggressive, non-combustible gases
non-aggressive, non-combustible gases
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
address range 0...247 selectable
Signal filtering
0s, 1s, 10s
Electrical connection
AWG 24 - 16, via push-in terminal
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief,
exchangeable, max. inner diameter 10.4 mm) or
M12 connector (male, 5-pin, A-code)
according to DIN EN 61076-2-101 (optional on request)
exchangeable, max. inner diameter 10.4 mm) or
M12 connector (male, 5-pin, A-code)
according to DIN EN 61076-2-101 (optional on request)
Housing dimensions
4.96 x 3.54 x 1,97 in (Tyr 2)
Cable gland
2x M 16 x 1.5; including strain relief, exchangeable
Long-term stability
± 1 % per year
Sum of Linearity+hysteresis
< ± 1 % of final value
Temperature drift values
± 0.1 %/ K
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) enclosure only! (PLEUROFORM IP 30)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU