temperature Luftfeuchtigkeit

Dew point control switches HYGRASGARD® TW-Modbus-T3

Product group: WG01

Low availability.

Usually ships in 3 to 5 days
$ 700.33
$ 588,51 + sales tax + shipping
+

Description

Dew point control switches HYGRASGARD® TW - Modbus - T3
Patented quality product
(pro-dynamic cross convection patent no. DE 10 2012 015 726.6)

Calibratable dew point control switch HYGRASGARD® TW - Modbus - T3 (compact variant incl. strap) or TW - Modbus - external (detached variant), with Modbus connection, in an impact-resistant plastic housing with quick-locking screws, optionally with/ without display, to exactly detect the relative humidity (0…100% RH) and the temperature (–35...+80 °C) and to detect various parameters in humidity measurement. The dew formation in particular is reliably determined thanks to its patented measuring method, the pro-dynamic cross-convection (no conductivity measurement). International system of units SI (default) can be switched to Imperial (via Modbus).

The surface-contact sensor is applied in a non-aggressive, dust-free environment and is suitable for installation in ceilings, ducts and devices. It is used in the refrigeration, air conditioning and clean room technology, engineering rooms, hotels and conference facilities.

A long-term stable, digital humidity and temperature sensor guarantee exact measurement results. These measurands are used to internally calculate the following parameters that can be retrieved via Modbus: relative humidity, absolute humidity, mixture ratio, dew point, enthalpy (ignoring atmospheric air pressure) and ambient temperature.
Innovative Modbus sensor with galvanically separated RS485-Modbus-interface, selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in curent-free state, internal LEDs for telegram status display, two separate push-in terminals and large three-line display (illuminated; with customised programming in the 7-segment and dot-matrix range). The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

Technical details

Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Data points
Temperature [°F], relative humidity [% RH],
dew point [°F], absolute humidity [gr/ft³],
mixture ratio [gr/lb], enthalpy [Btu/lb]
Deviation of humidity
typical ± 2.0 % (20…80 % RH); at + 25 °F, otherwise ± 3.0 %
Temperature deviation
typically ± 0.4 °F at +77 °F
Sensor
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
Sensor protection
membrane filter
Measuring range
0...100 % RH (humidity)
-31...+176 °F (temperature)
Measuring ranges
-31...+176 °F
0...100 % RH
Zero point offset
± 10 % RH (humidity)
± 9 °F (temperature)
Ambient temperature
-22...+158 °F
Medium
clean air and
non-aggressive, non-combustible gases
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
4 s / 32 s
Process connection
endless metal strap with metal tightener,
300 mm, for pipes up to 3 ''
(included in scope of delivery)
Electrical connection
AWG 24 - 16, via push-in terminal
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Protection type housing
IP 65
Prices are now displayed including taxes