Surface-contact temperature measuring transducer/ pipe surface-contact sensor ALTM 2 - EtherCAT P
temperature Temperature

Surface-contact temperature measuring transducer/ pipe surface-contact sensor THERMASGARD® ALTM 2 - EtherCAT P

Product group: WG02

In Stock

Usually ships in 1 to 3 days
438,41 €
368,41 € + VAT + shipping
+

Description

Surface-contact temperature measuring transducer/ pipe surface-contact sensor THERMASGARD® ALTM 2 - EtherCAT P
Networkable THERMASGARD® ALTM2 - EtherCATP surface-contact temperature measuring transducer (detached version) with M8 plug-in connector (EtherCATP-encoded), Bluetooth-enabled, in an impact resistant plastic housing with quick-locking screws, optionally with/without display and bar graph, cable sensor with pipe feeder, incl. strap.
The pipe surface-contact sensor serves to detect the temperature on lines, pipes (e.g. cold and warm water) or on heating sections for heating control. The sensor is factory-calibrated.
EtherCATP-enabled measuring transducer for industrial requirements with maximum reliability: includes easy PLC integration using the devices ESI configuration file, diagnostics (such as communication failure counter), advanced setting options, access to historical data (min/max) and sensor service interval determination. Optionally with large back-lit three-line display (customised programming in the 7-segment and dot-matrix ranges) and bar graph (7-digit, LEDs freely configurable) for graphical display, e.g. as a traffic light indicator.

Technical details

Voltage supply
24VDC via EtherCATP (US)
Power consumption
< 3 W
Radio technology
Bluetooth (LE)
Sensor
Pt1000, DIN EN 60751, class B (Perfect Sensor Protection at IP68)
Sensor protection
Sensor sleeve made from stainless steel V4A (1.4571), Ø = 6 mm,
nominal length (NL) = 50 mm (optional 30...400 mm)
Measuring range
–50...+150 °C
Accuracy
typically ± 0.2 K at +25 °C
Ambient temperature
Measuring transducer –30...+70 °C
Medium
clean air and
non-aggressive, non-combustible gases
Process connection
Endless strap made from metal,
Ø = 13 - 92 mm (¼ - 3"), l = 300 mm (included in delivery scope)
Cable connection
M8 plug-in connector, EtherCATP-encoded
Dimensions
126 x 90 x 50 mm (Tyr 2)
sensor cable
Silicone, SiHF, 2 x 0,25 mm²; cable length (KL) = 1.5 m
(other lengths and jacket materials, e.g. PTFE or
glass fibre with steel mesh, available on request)
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) sleeve humidity-tight (standard)
IP 68 (according to EN 60 529) sleeve water-tight (optional)
IP 54 (according to EN 60 529) housing / with glass fibre cable (optional)
Standards
CE conformity, according to EMC Directive 2014/ 30/ EU,
according to RED 2014/ 53/ EU

Accessories