Room humidity, temperature, air quality and CO2 sensor RTM-CO2-SD-U
temperature Temperature
temperature CO2

Multifunctional room sensors and measuring transducers AERASGARD® RTM-CO2-SD-U

Item no. 1501-61B2-1001-200
EAN 4251325616377
Product group: WG02

In Stock

Usually ships in 1 to 3 days
281,42 €
281,42 €
236,49 € + VAT + shipping
+

Description

Room humidity, temperature, air quality and CO2 sensor AERASGARD® RFTM-CO2 / RFTM-LQ-CO2
Maintenance-free room sensor AERASGARD® RTM - CO2 - SD with active output, automatic calibration (fixed), in an elegant plastic housing with snap-on cover, for determining the CO2 content of the air (0...2000 ppm) and the temperature (0...+50°C). The measuring transducer converts the measured values into a standard signal of 0-10 V.
The air quality is detected by a VOC sensor (mixed gas sensor for volatile organic substances). This sensor determines the load of contaminated gases in the room air, such as from cigarette smoke, body perspiration, exhaled breathing air, solvent vapours, emissions from building components, etc. Low, medium or high VOC sensitivity can be selected depending on the expected air contamination.

Technical details

Power consumption
< 1.5 W/ 24 V DC typical;
< 2.9 VA/ 24 V AC typical;
peak current 200 mA
Data points
temperature, carbon dioxide (CO2)
Deviation of humidity
typical ± 2 % RH (20…80 % RH ); at + 25 °C, otherwise ± 3 %
Measuring range, temperature
0...+ 50 °C (output equivalent to 0 -10 V or 4...20 mA)
Operating range, temperature
0...+50 °C
Temperature deviation
typically ± 0.2 K at +25 °C
Output, temperature
0 -10 V (fixed)
Service life
> 60 months (under normal load conditions)
depending on the type of loading and gas concentration
Measuring range, CO2
0...2000 ppm (fixed)
Sensor, CO2
optical NDIR sensor
(non-dispersive infra-red technology),
with manual calibration (via zero button) and
automatic calibration (fixed)
Output, CO2
0 -10 V (fixed)
Measuring accuracy, CO2
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Relay output
without changeover contact
Warm up time
approx. 1 hour
Response time
< 2 minutes
Output
0 - 10 V
Output
0 -10 V (fixed)
Measuring range
0...2000 ppm
Ambient temperature
0...+50 °C
Electrical connection
0.14 - 1.5 mm² via terminal screws
Housing
plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions
98 x 98 x 33 mm (Baldur 2)
Installation
wall mounting or on in-wall flush box, Ø 55 mm,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation
Long-term stability
< 2 % in 15 years
Protection class
III (according to EN 60 730)
Protection type
IP 30 (according to EN 60 529)
Protection type housing
IP 30
Standards
CE conformity, electromagnetic compatibility
according to EN 61 326, EMC Directive 2014/ 30/ EU,
Low Voltage Directive 2014/ 35/ EU