Outside temperature / wet room temperature measuring transducer
THERMASGARD® ATM 2
Calibratable THERMASGARD® ATM 2 outside temperature measuring transducer with eight switchable measuring ranges, external sensor, continuous output, housing made of impact resistant plastic with quick-release screws, optionally with/without display, with cable gland or M12 connector according to DIN EN 61076-2-101.
The transmitter serves to detect outside temperatures, temperatures in wet rooms, and is installed e.g. on outside walls, in cold storage buildings and greenhouses, in the industrial sector and in agriculture. Installation in outdoor areas is preferably performed at the north side of a building or in a protected place. In cases of direct solar irradiation, we recommend the use of our WS 01 or WS 04 sun and ball-impact protection hood (accessory) or the device version with the installed SS 02 protection hood (on request).
The transmitter serves to detect outside temperatures, temperatures in wet rooms, and is installed e.g. on outside walls, in cold storage buildings and greenhouses, in the industrial sector and in agriculture. Installation in outdoor areas is preferably performed at the north side of a building or in a protected place. In cases of direct solar irradiation, we recommend the use of our WS 01 or WS 04 sun and ball-impact protection hood (accessory) or the device version with the installed SS 02 protection hood (on request).
The sensor is factory-calibrated and can be fine-tuned to ambient conditions by an expert.
Technical details
Power consumption
< 1,0 W/ 24 V DC
< 2,2 VA/ 24 V AC
< 2,2 VA/ 24 V AC
Sensor
Pt1000, DIN EN 60751, class B
(Perfect Sensor Protection)
(Perfect Sensor Protection)
Connection type
2- or 3-wire connection
Measuring ranges
multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
operating range –30...+70 °C
with manual zero point correction (± 10 K)
see table (other ranges optional)
operating range –30...+70 °C
with manual zero point correction (± 10 K)
Accuracy
typically ± 0.2 K at +25 °C
Ambient temperature
Measuring transducer –30...+70 °C
Process connection
by screws
Protective tube
stainless steel V4A (1.4571), Ø 6 mm, NL = 65 mm
Electrical connection
0.14 - 1.5 mm² via terminal screws
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
M12 connector according to DIN EN 61076-2-101 (optional on request)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
max. inner diameter 10.4 mm
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU