Description
Immersion/ screw-in/ duct
temperature measuring transducer THERMASGARD® TM 65 - EtherCAT P
temperature measuring transducer THERMASGARD® TM 65 - EtherCAT P
Networkable THERMASGARD® TM65 - EtherCAT P temperature measuring transducer with sensor tube with M8 plug-in connector (EtherCATP-encoded), Bluetooth-enabled, in an impact resistant plastic housing with quick-locking screws, optionally with/without display and bar graph.
The duct temperature transmitter serves to detect the temperature in liquid or gaseous media. Use our stainless steel thermowells for aggressive media. The sensor device is used in heating engineering, ventilation and air conditioning ducts, pipes, storage systems, compact district heating stations, warm and cold water systems, oil and lubrication cycle systems, machine and systems engineering and the entire industry sector. The sensor is factory-calibrated.
The duct temperature transmitter serves to detect the temperature in liquid or gaseous media. Use our stainless steel thermowells for aggressive media. The sensor device is used in heating engineering, ventilation and air conditioning ducts, pipes, storage systems, compact district heating stations, warm and cold water systems, oil and lubrication cycle systems, machine and systems engineering and the entire industry sector. The sensor is factory-calibrated.
EtherCATP-enabled measuring transducer for industrial requirements with maximum reliability: includes easy PLC integration using the devices ESI configuration file, diagnostics (such as communication failure counter), advanced setting options, access to historical data (min/max) and sensor service interval determination. Optionally with large back-lit three-line display (customised programming in the 7-segment and dot-matrix ranges) and bar graph (7-digit, LEDs freely configurable) for graphical display, e.g. as a traffic light indicator.
Technical details
Voltage supply
24VDC via EtherCATP (US)
Power consumption
< 3 W
Radio technology
Bluetooth (LE)
Sensor
Pt1000, DIN EN 60751, class B
(Perfect Sensor Protection)
(Perfect Sensor Protection)
Measuring range
–50...+150 °C
Accuracy
typically ± 0.2 K at +25 °C
Ambient temperature
Measuring transducer –30...+70 °C
Medium
Clean air and non-aggressive, non-combustible gases;
liquids depending on selected immersion sleeve (accessory)
liquids depending on selected immersion sleeve (accessory)
Protective tube
stainless steel, 1.4571, V4A, Ø = 6 mm
Cable connection
M8 plug-in connector, EtherCATP-encoded
Dimensions
126 x 90 x 50 mm (Tyr 2)
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 54 (according to EN 60 529) when built-in
Standards
CE conformity, according to EMC Directive 2014/ 30/ EU,
according to RED 2014/ 53/ EU