Duct humidity sensor/ Duct humidity and temperature sensor KFTF-20-I Q LCD
temperature Luftfeuchtigkeit
temperature Temperature

Duct humidity and temperature sensor HYGRASGARD® KFTF-20-I Q LCD

Item no. 2003-4152-2100-001
EAN 4251325622316
Product group: WG02

Currently not available

365,78 €
435,28 € incl. VAT + shipping
+

Description

Duct humidity and temperature sensor HYGRASGARD® KFTF
Calibratable HYGRASGARD® KFF - SD / KFTF - SD duct humidity/temperature transmitters (± 2,0%), with plastic sinter filter (metal sinter filter optional), housing made of impact resistant plastic with snap-on cover, with cable gland (or optional M12 connector according to DIN EN 61076-2-101).

Calibratable HYGRASGARD® KFF / KFTF or KFF - 20 / KFTF - 20 duct humidity/temperature transmitters (±2,0% or ±1,8%, respectively) with plastic sinter filter (metal sinter filter optional), housing made of impact resistant plastic with quick-locking screws, optionally with/without display, with cable gland (or optional M12 connector according to DIN EN 61076-2-101).
The sensor devices measure relative humidity and/or air temperature and convert the measurands into a standard signal of 0-10 V or 4...20 mA. They support four switchable temperature ranges and are applied in non-aggressive dust-free atmospheres in refrigeration, air conditioning, ventilation and cleanroom engineering. These measuring transducers provide precise detection of humidity. A digital long-term stable sensor is used as measuring element for humidity. The sensor is factory-calibrated and can be fine-tuned to ambient conditions by an expert.

Technical details

Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Power consumption
< 1.1 VA/ 24 V DC ; < 2.2 VA/ 24 V AC
Data points
temperature [°C], relative humidity [% RH]
Working resistance
Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant
Measuring range, humidity
0...100 % RH
(output corresponding to 4...20 mA)
Deviation of humidity
typical ± 1.8 % (10…90 % RH ); at + 25 °C, otherwise ± 2,0 %
Output, humidity
4...20 mA
Measuring range, temperature
multi-range switching
with 4 switchable measuring ranges
–35...+35 °C; –35...+75 °C; 0...+50 °C; 0...+80 °C
(output corresponding to 0 -10 V or 4...20 mA)
Output, temperature
4...20 mA
Measuring accuracy
typically ± 0.2 K at +25 °C
Sensor protection
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
Measuring ranges
–35...+35 / –35...+75 / 0...+50 / 0...+80 °C
0...100 % RH
Accuracy
typical ± 1,8 % RH (10…90 % RH ); at + 25 °C, otherwise ± 2 %
Ambient temperature
storage –35...+85 °C;
operation – 30...+75 °C, non-precipitating
Process connection
by mounting flange, plastic
(included in the scope of delivery)
Protective tube
PLEUROFORM, material polyamide (PA6), with torsion protection,
Ø 20 mm, NL = 235 mm (optionally 100 mm), vmax = 30 m/s (air)
(option on request in stainless steel V2A (1.4301), Ø 16mm)
Electrical connection
2-, 3- or 4-wire connection
0.14 -1.5 mm ² via terminal screws on circuit board
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Housing dimensions
126 x 90 x 50 mm (Tyr 2)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Long-term stability
± 1 % per year
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) Housing tested,
TÜV SÜD, Report No.713139052 (Tyr 1)
Protection type housing
IP 65
Standards
CE conformity,
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
Optional
three-line display with illumination, cutout 70 x 40 mm (W x H),
for displaying ACTUAL temperature and/ or ACTUAL humidity

Accessories