Luftfeuchtigkeit
Temperature
Outside humidity and temperature sensor HYGRASGARD® AFTF-SD-Modbus
Product group: WG01
Description
Outside humidity and temperature sensor
HYGRASGARD® AFTF - SD - Modbus
Quality product for the HVAC sector, accuracy ±2%
Calibratable HYGRASGARD® AFTF-SD-Modbus outside humidity and temperature sensor with Modbus connection, terminal box housing made of impact resistant plastic, housing cover with quick-locking screws, with/without optional display.
Calibratable HYGRASGARD® AFTF-SD-Modbus outside humidity and temperature sensor with Modbus connection, terminal box housing made of impact resistant plastic, housing cover with quick-locking screws, with/without optional display.
The universal on-wall sensor serves to detect various parametres in humidity measuring. Measurands include relative humidity and ambient air temperature. These measurands are used to calculate various parametres internally. The Modbus device can serve to retrieve the following parametres: relative humidity [%r.H.], absolute humidity [g/m³], mixture ratio [g/kg], dew-point temperature [°C], enthalpy [kJ/kg] (ignoring atmospheric air pressure) and ambient temperature [°C].
The temperature transmitter is used in non-aggressive, dust-free environments, in refrigeration, air conditioning and cleanroom engineering, in hotels, engineering rooms, meeting and conference facilities. The measuring transducer provides precise detection of temperature and humidity. A digital, long-term stable sensor is used as a measuring element for humidity and temperature. Fine adjustment by the user is possible.
The temperature transmitter is used in non-aggressive, dust-free environments, in refrigeration, air conditioning and cleanroom engineering, in hotels, engineering rooms, meeting and conference facilities. The measuring transducer provides precise detection of temperature and humidity. A digital, long-term stable sensor is used as a measuring element for humidity and temperature. Fine adjustment by the user is possible.
Technical details
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
15…36 V DC
Power consumption
< 1,0 W/ 24 V DC
< 2,2 VA/ 24 V AC
< 2,2 VA/ 24 V AC
Data points
Temperature [°C], relative humidity [% RH],
dew point [°C], absolute humidity [g / m3],
mixture ratio [g / kg], enthalpy [kJ / kg]
dew point [°C], absolute humidity [g / m3],
mixture ratio [g / kg], enthalpy [kJ / kg]
Deviation of humidity
typical ± 2.0 % (20…80 % RH); at + 25 °C, otherwise ± 3.0 %
Temperature deviation
typically ± 0.6 K at +25 °C
Sensor
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
with integrated temperature sensor,
low hysteresis, high long-term stability
Sensor protection
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
Measuring ranges
–35...+80 °C
0...100 % RH
0...100 % RH
Zero point offset
± 10 % RH (humidity)
± 5 °C (temperature)
± 5 °C (temperature)
Ambient temperature
–30...+70 °C
Medium
clean air and
non-aggressive, non-combustible gases
non-aggressive, non-combustible gases
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
address range 0...247 selectable
Process connection
by screws
Protective tube
stainless steel V2A (1.4301), Ø 16 mm, NL = 55 mm
Cable gland
2x M 12 x 1.5 (Y-adapter); with strain relief,
exchangeable, max. inner diameter 6 mm
exchangeable, max. inner diameter 6 mm
Long-term stability
± 1 % per year
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Protection type housing
IP 65
Standards
CE conformity
according to EMC Directive 2014/ 30/ EU,
according to EN 61 326
according to EMC Directive 2014/ 30/ EU,
according to EN 61 326