Room temperature sensor with operating element THERMASGARD® RTF xx
Room temperature sensor THERMASGARD® RTF xx with passive output, in attractive plastic housing (Baldur 1 / Baldur 2) with snap-on enclosure cover, base with 4-hole attachment, for mounting on vertically or horizontally installed in-wall flush boxes, with predetermined breaking point for on-wall cable entry. Available as a room control unit in various type versions with control elements such as setpoint potentiometer (%), rotary switch (max. 5-step), rocker switch, push-button or coloured LEDs for displaying the operating states.
This residential room temperature sensor is used to detect/ display the temperature (–22…+158 °F) in closed, dry rooms, in apartments, in cinemas, supermarkets, storage rooms, office and business facilities.

Technical details

Output, potentiometer
Standard 1 kOhm, max. 0.1 W
(other values optionally available upon request,
e.g. 100 Ohm, 2.5 kOhm, 5 kOhm, 10 kOhm),
with angle of rotation limiter
Unit versions with active potentiometer (0 -10 V), see RTM xx
Measuring range
-22...+158 °F
Process connection
by screws
Electrical connection
AWG 26 - 16 via terminal screws,
on safety extra-low voltage max. 24 V DC only
Housing
plastic, material ABS,
colour pure white (similar to RAL 9010)
Permissible air humidity
max. 90 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 30 (according to EN 60 529)
Sensor
NTC10kOhm Precon
Connection type
2-wire connection
Testing current
< 2.0 mW
Dimensions
3.35 x 3.35 x 1.06 in (Baldur 1)
Installation
wall mounting or on in-wall flush box, Ø 2.2 in,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation
Optional
4-wire connection
Baldur 2
special versions available upon request
Features
Potentiometer: Swelling arrow type (standard print is filled with centre position;
optionally wedge-shaped or with marking points –3K... +3K)