temperature Luftfeuchtigkeit
temperature CO2
temperature Temperature

Room operating unit (interface) - 24 V RYMASKON® RYM 1301-RH-CO2-MOD-AP-BL

Item no. RYM1-3011-M611-005
EAN 4251325632940
Product group: WG02

Low availability.

Usually ships in 3 to 5 days
$ 1,185.75
$ 1.411,04 incl. sales tax + shipping
+

Description

Room operating unit (interface) RYMASKON® 1000 Interface
The room control units of the RYMASKON® 1000 / 2000 / 3000 series are designed for control (up to 5 climate zones) in residential, hotel and office rooms and individually regulate the heating, cooling and fan levels of the internal rooms. The controller variants can be operated as stand-alone units thanks to the integrated control functions PI, PWM or 2-/3-point control. The product family is characterised by its elegant design, intuitive operation and the many possible combinations of the individual components.

The RYMASKON® 1000 room control units (interface) are used for controlling temperature, fans, sun protection (Venetian blinds, shutters) or light (with dimming function). The room control units make the setpoints available to the BMS either via conventionally wired Modbus or via the wireless, radio-based W-Modbus. Visual indication takes place on a 2" TFT display, where as the unit is controlled via capacitative keys (touch keys).
In addition to the integrated temperature and humidity sensor, sensors for CO2 and VOC are available as an option. An input for a passive temperature sensor (NTC10K) and an input for a potential-free contact are additionally available. This allows a window contact or a condensation control switch to be connected, for example. This provides all options for air-conditioning of the rooms according to individual requirements.
All unit types are available in the contemporary housing Iduna 3 (4.4 x 3.5 x 0.94 in) in white or black colour. Wall-mounting is performed on standard in-wall flush boxes or on-wall.

Technical details

Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
typically < 3 W at 24 V DC; typically < 4.5 VA at 24 V AC
Measuring range, humidity
0...100 % RH
Measuring range, temperature
0...+50 °C / +32...+122 °F
Data points
Temperature [°C] [°F], elative humidity [% RH], carbon dioxide (CO2) [ppm]
Measuring accuracy
typically ± 0.9 °F at +77 °F
Inputs
1 NTC10K (configurable as a digital input)
1 digital input for potential-free switches
Output
Modbus
Accuracy
typical ± 2.0 % (20…80 % RH); at + 77 °F, otherwise ± 3.0 %
Ambient temperature
+32...+122 °F (operation); –22...+158 °F (storage)
Electrical connection
AWG 24 - 16, using push-in terminals
Measuring range, CO2
0...2000 ppm
Sensor, CO2
digital photoacoustic NDIR-CO2 sensor
(non-dispersive infra-red technology),
with automatic calibration and high long-term stability
Permissible air humidity
0...90 % RH (non-precipitating air)
Measuring accuracy, CO2
typically ±50 ppm, ±3 % of the measured value at +77 °F
Protection type
IP 30 (according to EN 60 529)
Function
Temperature, fan, sun protection and light (see type table)
Operating elements
Capacitive keys (up to 10 keys, depending on type)
for setting the target temperature, fan stages, presence message, sensor values,
and for operating sun protection and light
Setpoint capture
setpoint (temperature, presence)
Communication
Modbus (RTU cable),
Slave, address range 1…247, RS 485 interface, max. 32 units,
9600 / 19200 / 38400 / 57500 Baud,
8N1, even / odd parity, 1 / 2 stop bits
Housing
Plastic, flame retardant (UL 94 V-0), PC/ABS material,
colour white (similar to RAL 9016) or black (similar to RAL 9004)
Housing dimensions
4.4 x 3.5 x 0.94 in (W x H x D) (Iduna 3)
in-wall: + 0.91 in (D), sensor protection: + 0.87 in (H)
Standards
CE-conformity according to
EMC Directive 2014/ 30/ EU (Modbus) or
Radio Directive 2014/ 53/ EU (W-Modbus)
Display
TFT display, 2" (1.6 x 1.2 in), 320 x 240 x 3 pixels (RGB),
LED backlighting, viewing angle ± 85°