temperature Temperature

Outside temperature/ wet room temperature measuring transducers THERMASGARD® ATM2-Modbus-T3 LCD

Item no. 1101-12C6-4000-000
EAN 4251325618555
Product group: WG01

Low availability.

Usually ships in 3 to 5 days
$ 814,85
$ 814.85
$ 684,75 + sales tax + shipping
+

Description

Outside temperature/ wet room temperature measuring transducers THERMASGARD® ATM 2 - Modbus - T3
Calibratable outside temperature measurement transducer THERMASGARD® ATM 2 - Modbus - T3, with Modbus connection, in an impact-resistant plastic housing with quick-locking screws, optionally with/ without display, measures temperature (–50...+150 °C). International system of units SI (default) can be changed to imperial (via Modbus).

The on-wall sensor is used to detect the temperature in gaseous media. It is used outside or in wet rooms, in cold storage buildings and greenhouses, in the industrial sector and in agriculture. Installation on outside walls is preferably performed on the north side or in a protected place. In case of direct solar irradiation, we recommend using our sun and ball-impact protection hood WS 01 or WS 04 (accessories).
Innovative Modbus sensor with galvanically separated RS485 Modbus interface, selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal LEDs for telegram status display, two separate push-in terminals and large three-line display (illuminated, with customised programming in the 7-segment range and dot-matrix range). Uses internal diagnostics to detect sensor breakage or sensor short circuit as errors. The error messages can be retrieved via Modbus and are shown on the display. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

Technical details

Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Data points
température [°C] [°F]
Temperature deviation
typically ± 0.4 °F at +77 °F
Sensor
Pt1000, DIN EN 60751, class B
Measuring range
-58...+302°F
Accuracy
typically ± 0.4 °F at +77 °F
Zero point offset
± 18 °F
Ambient temperature
Measuring transducer –22 … +158°F
Medium
clean air and
non-aggressive, non-combustible gases
Error detection
sensor breakage, sensor short circuit
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
0,3 s / 1 s / 10 s
Communication
Modbus RTU (RS485 interface for RTU cable)
Process connection
by screws
Electrical connection
AWG 24 - 16, via push-in terminal
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Units
switchable metric / imperial
Internal diagnostics
Error 1 at sensor breakage
Error 2 at sensor short circuit
Cable connection
cable gland, plastic
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 0,3 - 0,5 in) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Housing dimensions
108 x 78.5 x 45.8 mm (Tyr 3 with display)
Cable gland
2x M 20 x 1.5; with strain relief, replaceable,
inner diameter 0.3 - 0.5 in
Standards
CE conformity according to EMC Directive 2014 / 30 /EU
Optional
Display with illumination, three-line, programmable,
cutout approx. 51 x 29 mm (W x H),
for displaying the actual temperature or
an individually programmable display value (The Modbus
interface allows the display to be individually configured in the
7-segment area and in the dot-matrix area.)
Features
Display with illumination, three-line, programmable,
cutout approx. 2.0 x 1.1 in (W x H),
for displaying the actual temperature or
an individually programmable display value

Accessories

Prices are now displayed including taxes