ACO2 MODBUS

AERASGARD® ACO2 MODBUS

Art.nr. 1501-7110-6001-200
EAN 4 251325 613499

The maintenance-free, microprocessor-controlled AERASGARD® AFTM - LQ - CO2 - Modbus and ACO2 - Modbus ⁄ ALQ - CO2 - Modbus with Modbus connection, with ⁄ without optional display, is designed for on-wall installation and is used to monitor all measurands of relevance to the climate inside a room. These are the measurands air humidity, temperature, CO2 concentration as well as air quality (VOC). By using a single device to monitor all four measurands, it is possible to effectively monitor and regulate the entire room climate. It measures CO2 in the range of 0...5000 ppm, VOC at one of three selectable sensitivity levels LOW / MEDIUM / HIGH, temperatures in the range of –35...+80 °C, as well as relative air humidity from 0...100 % r.H.

The relative humidity (% r.H.) quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature. A digital, long-term stable sensor used as measuring element for relative air humidity and temperature guarantees exact measurement results.

The CO2 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detection range of the sensors is calibrated for standard applications such as monitoring residential rooms and conference rooms. Room ventilation on an as-needed basis, improved well-being and customer benefit, increased comfort as well as reduced operating costs through energy conservation are just some of the benefits of employing the AERASGARD® CO2 sensor.

The explanations above demonstrate that there are applications for CO2 measurements, for VOC measure ments, but from our perspective, above all, for a combination of both measurands. The crucial factor in this respect is that both of these measurands are not convertible into each other and derivations to or from one another cannot be made. An NDIR CO2 measuring instrument measures selectively and cannot detect any VOC; a VOC mixed gas sensor cannot recognize CO2 molecules.

326,40 € netto
Voltage supply 24 V AC ⁄ DC (± 10 %)
Power consumption < 4.4 W ⁄ 24 V DC typical; < 6.4 VA ⁄ 24 V AC typical;
peak current 200 mA
Data points temperature, relative humidity,
air quality (VOC), carbon dioxide (CO2),
atmospheric pressure
Measuring range, CO2 0...5000 ppm
Sensor, CO2 optical NDIR sensor (non-dispersive infra-red technology)
with automatic and manual calibration
Measuring accuracy, CO2 ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2 ± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C
(whichever is higher)
Pressure dependence ± 0,13 % ⁄ mm Hg
Gas exchange by diffusion
Response time < 2 minutes
Ambient temperature –10...+60 °C
Bus protocol Modbus (RTU mode),
address range 0...247 selectable
Signal filtering 4 s / 32 s
Process connection by screws
Protective tube stainless steel, Ø 16 mm, NL = 55 mm
Electrical connection 0.14 - 1.5 mm2, via push-in terminal
Enclosure plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted ⁄ Phillips head - combination),
colour traffic white (similar to RAL 9016),
enclosure cover for display is transparent !
Enclosure dimensions 126 x 90 x 50 mm (Tyr 2)
Cable gland 2x M 16 x 1.5; including strain relief, exchangeable
Long-term stability < 2 % in 15 years
Protection class III (according to EN 60 730)
Protection type IP 65 (according to EN 60 529)
Standards CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014 ⁄ 30 ⁄ EU
Type Art.nr. Prijs
KA-2 1906-1200-0000-100 0,00 €

S+S Regeltechnik - voordelen tot de vijfde macht

Meer te weten komen

Nieuws van S+S Regeltechnik

BeursnieuwsAlle aangeven

 

SPS IPC Drives – S+S Regeltechnik will be there
27. - 29.11.2018

Booth 10.1-120
Be our guest at Europe's leading trade fair for electric automation from 27 to...
meer

 

S+S Regeltechnik at CHILLVENTA 2018
16. - 18.10.2018

Booth 5-305
We are pleased to return and exhibit again at CHILLVENTA this fall. As...
meer

Overzicht van alle beursdata

ProductnieuwsAlle aangeven

 

HYGRASGARD® VFF ⁄ VFTF - Humidity and temperature measuring transducer for installation in showcases and display cabinets

This new device from S+S measures temperature and humidity using a digital sensor designed for...
meer

 

Good room climate is measurable – AERASGARD® RCO2-SD und KCO2-SD

With immediate effect, our room and duct sensors for measuring the CO2 concentration in air are now...
meer

Beursnieuws

CHILLVENTA 2018 | 16. - 18.10.2018 | Booth 5-305

meer

Abonneren op Newsletter

Blijf altijd geïnformeerd over onze producten en nieuws rond S+S Regeltechnik.