Efficiënt, koppelbaar en comfortabel

Elegant uiterlijk, aanraakoppervlak, groot display, voor Modbus-geschikt

RYMaskon

Multi-funtional duct sensor

Multi-functional duct sensor for monitoring and control of heating, ventilation and air-conditioning systems

PREMASGARD® 814x-Modbus

Good room climate is measurable!

Active and Modbus capable room sensors for temperature, humidity and CO2 now also for in-wall installation!

AERASGARD® FSCO2

All quite relative

Pressure measuring transducer for gaseous and liquid media in cost-efficient Standard version for 0 to 16 bar

PREMASGARD® SHD-SD

Für jede Anwendung die richtige Lösung

RCO2-W DISPLAY

AERASGARD® RCO2-W-DISPLAY

Art.nr. 1501-61B0-7321-200
EAN 4 251325 613130

The maintenance-free microprocessor-controlled room sensor AERASGARD® RCO2 - SD with automatic calibration (fixed) is used for recording the CO2 content of the air within a range of 0...2000 ppm. The measurement value is converted into standard signal of 0 -10 V.

The maintenance-free microprocessor-controlled room sensor AERASGARD® RCO2 - W with automatic calibration (can be deactivated via DIP switches) is used for detecting the CO2 content of the air within a range of 0...2000 ppm or 0...5000 ppm. The measurement value is converted into standard signal of 0 -10 V or 4...20 mA. Optional with traffic light indicator (five coloured LEDs).

Elegant enclosure made of plastic, with snap-on lid, based with 4-hole attachment, for installation on vertically or horizontally installed flush-mounted boxes, with predetermined breaking point for surfacemounted connection or in enclosure made of stainless steel (top and bottom parts are stainless steel, the cover is screwed on), vandal-proof version e.g. for schools, barracks and public buildings.

The CO2 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detection range of the CO2 sensor is calibrated for standard applications such as monitoring residential rooms and conference rooms. Room ventilation on an as-needed basis, improved well-being and customer benefit, increased comfort as well as reduced operating costs through energy conservation.

261,33 € netto
Voltage supply 24 V AC ⁄ DC (± 10 %)
Power consumption < 1.5 W ⁄ 24 V DC typical;
< 2.9 VA ⁄ 24 V AC typical;
peak current 200 mA
Output, CO2 0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring accuracy typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2 ± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C
(whichever is higher)
Pressure dependence ± 0,13 % ⁄ mm Hg
Gas exchange by diffusion
Relay output with potential-free changeover contact 24 V (assignment selectable via DIP switches)
Warm up time approx. 1 hour
Response time < 2 minutes
Output 0 -10 V  or  4...20 mA,  working resistance  < 800  Ω
(selectable via DIP switches) 
with offset potentiometer (± 10 % of the measuring range
Sensor
Optical NDIR sensor (non-dispersive infra-red technology),
with manual calibration (via zero button), 
with automatic calibration (can be deactivated via DIP switches)
Measuring range 0...2000 ppm or 0...5000 ppm (selectable via DIP switches)
Ambient temperature 0...+50 °C
Electrical connection 0.14 - 1.5 mm² via terminal screws
Enclosure plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions 98 x 98 x 33 mm (Baldur 2)
Installation wall mounting or on in-wall flush box, Ø 55 mm,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top ⁄ bottom in case of plain on-wall installation
Long-term stability < 2 % in 15 years
Protection class III (according to EN 60 730)
Protection type IP 30 (according to EN 60 529)
Standards CE conformity, electromagnetic compatibility
according to EN 61 326, EMC Directive 2014 ⁄ 30 ⁄ EU,
Low Voltage Directive 2014 ⁄ 35 ⁄ EU
Display with display for displaying the actual CO2 content in ppm

S+S Regeltechnik - voordelen tot de vijfde macht

Meer te weten komen

Nieuws van S+S Regeltechnik

BeursnieuwsAlle aangeven

 

ISH beurs Frankfurt – S+S Regeltechnik kijkt naar u uit!
11. - 15.03.2019

Stand 10.3 A71
Op de ISH, 's werelds grootste beurs voor "belevingswereld badkamer, gebouw-,...
meer

Overzicht van alle beursdata

ProductnieuwsAlle aangeven

PREMASGARD® 814x-Modbus - Multi-funtional duct sensor

This bus capable and calibratable pressure measuring transducer enables the control of differential...
meer

 

Multi-functional duct sensor for monitoring and control of heating, ventilation and air-conditioning systems

This bus capable and calibratable pressure measuring transducer enables the control of differential...
meer

Beursnieuws

ISH | 11. - 15.03.2019 | Stand 10.3 A71

meer

Abonneren op Newsletter