Description
Two-phase frost protection thermostats
THERMASREG® FS-20
Electronic THERMASREG® FS-20 frost protection thermostat or frost monitor with switching relay output, continuous temperature and valve output (summation output 0–10 V) and control and cascading output (0–10 V), optionally with connection for a heating element, in an impact resistant plastic housing with quick-locking screws, with display by default and a fully active sensor rod made of copper.
The frost monitor is used to monitor air conditioning systems, heat exchangers, heating registers and similar systems, and protects against frost damage and freezing. Limit value underrun is detected at the coldest measuring point of the capillary tube. The sensor rod is active along its entire length. The device uses internal diagnostics to detect capillary breakage, power failure or electric damage to the sensor as errors, and the relay switches to frost automatically.
The frost monitor is used to monitor air conditioning systems, heat exchangers, heating registers and similar systems, and protects against frost damage and freezing. Limit value underrun is detected at the coldest measuring point of the capillary tube. The sensor rod is active along its entire length. The device uses internal diagnostics to detect capillary breakage, power failure or electric damage to the sensor as errors, and the relay switches to frost automatically.
The innovative 2-phase frost protection thermostat enables a simple combination of several devices (cascading) for on-demand, comprehensive frost monitoring. The delivery scope includes a set of MK-05-Kmounting clamps for expert attachment of the sensor rod.
Technical details
Voltage supply
24 V AC/ DC (± 10 %)
Load resistance
RL > 50 kOhm
Switch-on start-up time
< 1 min
Response time
t90 < 5 s
Input
1 x 0 -10 V control input DDC
1 x 0 -10 V ascading input
1 x 0 -10 V ascading input
Measuring range
0...+15 °C
Accuracy
typically ± 1 K (at +10 °C)
Process connection
by mounting clamps MK- 05 - K
(included in the scope of delivery)
(included in the scope of delivery)
Electrical connection
0.14 - 1.5 mm² via terminal screws
Output
1 x 0 -10 V output temperature (corresponding to 0...+15 °C)
1 x 0 -10 V output valve
(frost signal with control voltage and cascading)
1 x potential-free changeover contact (24 V),
range of adjustment 0...+15 °C
1 x 0 -10 V output valve
(frost signal with control voltage and cascading)
1 x potential-free changeover contact (24 V),
range of adjustment 0...+15 °C
Housing dimensions
126 x 90 x 50 mm (Tyr 2)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
max. inner diameter 10.4 mm
Current consumption
max. 100 mA at 24 V DC
Hysteresis of switching step
2K
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Ambient temperatures
Sensor and capillary tube: –20...+60 °C
(capillary tube at a distance of > 20 cm from the housing)
Housing: –15...+50 °C
Storage/ transport: –30...+70 °C
(capillary tube at a distance of > 20 cm from the housing)
Housing: –15...+50 °C
Storage/ transport: –30...+70 °C
Protection type
IP 65 (according to EN 60 529)*
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Sensor and capillary
Copper sensor rod, length of 3 m or 6 m,
active along the entire sensor length,
min. response length of 25 cm
active along the entire sensor length,
min. response length of 25 cm
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Features
display with illumination, three-line, cutout approx. 70 x 40 mm
(W x H), for displaying the actual temperature, measuring
range overrange/underrange of the set switch point (frost
protection temperature), and alarm indicator for "frost" or
"error" (capillary breakage, overvoltage/undervoltage)
(W x H), for displaying the actual temperature, measuring
range overrange/underrange of the set switch point (frost
protection temperature), and alarm indicator for "frost" or
"error" (capillary breakage, overvoltage/undervoltage)
Internal diagnostics
Error 1 in case of cable / capillary breakage
Error 2 in case of undervoltage / overvoltage
(relay automatically switches to frost)
Error 2 in case of undervoltage / overvoltage
(relay automatically switches to frost)