Efficient, convenient and network-enabled
Elegant appearance, touch-operated interface, large display, and Modbus-compatible
RYMaskonResistance thermometer THERMASGARD® RPTF 1 with passive output that is specifically used for temperature detection in larger rooms or halls. Due to the measuring method employed by this pendulum room temperature sensor in combination with its positioning in the room, an excellent measuring result that is representative of the room is achieved thanks to the uniform flow of ambient air around the sensor.
Sensor | Pt100, DIN EN 60751, class B |
---|---|
Sensor protection |
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable (optional metal sinter filter, Ø 16 mm, L = 32 mm) |
Connection type | 4-wire connection |
Testing current | < 1.0 mA |
Measuring range | –5...+60 °C |
Insulating resistance |
≥ 100 MΩ, at +20 °C (500V DC) |
Connection cable |
PVC; 1.5 m, H03VV-F, 2 x 0.25 mm², ends stripped with wire end sleeves (other lengths optional: 3 m, 6 m) |
Protective tube | stainless steelV2A (1.4301), Ø = 16 mm, L = 142 mm |
Connection cable |
PVC, H03VV-F, 2 x 0.5 mm2, ends stripped with wire end sleeves KL = approx. 1.5 m (other lengths optional) |
Humidity | < 95 % r. H. |
Protection class | III (according to EN 60 730) |
Protection type | IP 65 (according to EN 60 529) |
ISH Messe Frankfurt – S+S Regeltechnik looks forward to meeting you!
11. - 15.03.2019
Stand 10.3 A71
At the ISH, the world's leading trade fair for "The Bathroom Experience,...
more
Multi-functional duct sensor for monitoring and control of heating, ventilation and air-conditioning systems
This bus capable and calibratable pressure measuring transducer enables the control of differential...
more
Good room climate is measurable! - AERASGARD® FSCO2 ⁄ FSTM-CO2 ⁄ FSFTM-CO2-Modbus
Our multifunctional room sensors for measuring temperature, humidity and CO2 concentration can now...
more
ISH | 11. - 15.03.2019 | Stand 10.3 A71
more