Efficient, convenient and network-enabled
Elegant appearance, touch-operated interface, large display, and Modbus-compatible
RYMaskonCalibratable tube contact temperature measuring transducer THERMASGARD® ALTM 2 with eight switchable measuring ranges, internal or remote sensor, continuous output, strap and terminal box enclosure made of impact-resistant plastic, enclosure cover with quick-locking screws, with ⁄ without optional display. The surface-contact sensor is used for temperature detection on lines, pipes (e.g. cold and hot water) or on heating sections for heating system control. The tube sensors are factory-calibrated. Adjustment ⁄ fine adjustment by the user is possible (zero point offset is adjustable).
Voltage supply |
15...36 V DC depending on working resistance, residual ripple stabilised ± 0.3 V |
---|---|
Power consumption |
< 1,0 VA ⁄ 24 V DC
< 2,2 VA ⁄ 24 V AC |
Working resistance | Ra (ohm) = (Ub -14 V) ⁄ 0.02 A for I variant |
Temperature deviation | typically ± 0.2 K at +25 °C |
Output | 4...20 mA |
Sensor | Pt1000, DIN EN 60751, class B |
Connection type | 2- or 3-wire connection |
Measuring ranges |
multi-range switching with 8 switchable measuring ranges,
(other ranges optional) detached sensor variant: Tmax over 100 °C, operating range –50... +150 °C; with manual zero point correction (± 10 K) |
Ambient temperature | Measuring transducer –30...+70 °C |
Process connection |
endless metal strap and metal tightener (included in scope of delivery) |
Insulating resistance |
≥ 100 MΩ, at +20 °C (500V DC) |
Strap dimensions | Ø = 13 - 92 mm (¼ - 3"), L = 300 mm |
Electrical connection | 0.14 - 1.5 mm² via terminal screws |
Enclosure |
plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced, with quick-locking screws (slotted ⁄ Phillips head - combination), colour traffic white (similar to RAL 9016), enclosure cover for display is transparent ! |
Enclosure dimensions | 72 x 64 x 43.3 mm (Tyr 1 with Display) |
Cable gland |
2x M 12 x 1.5 (Y-adapter); with strain relief, exchangeable, max. inner diameter 6 mm |
Connection cable | silicone, SiHF, 2 x 0.25 mm², KL = 1.5 m |
Permissible air humidity | < 95 % r. H., non-precipitating air |
Protection class | III (according to EN 60 730) |
Protection type | IP 65 (according to EN 60 529) |
Standards |
CE conformity, electromagnetic compatibility according to EN 61326, according to EMC Directive 2014 ⁄ 30 ⁄ EU |
Display |
Display mit Beleuchtung, zweizeilig, Ausschnitt ca. 36 x15 mm (B x H), zur Anzeige der Ist -Temperatur und der Eigendiagnostik (Messbereichsüberschreitung, Messbereichsunterschreitung, Fühlerbruch, Fühlerkurzschluss) |
ISH Messe Frankfurt – S+S Regeltechnik looks forward to meeting you!
11. - 15.03.2019
Stand 10.3 A71
At the ISH, the world's leading trade fair for "The Bathroom Experience,...
more
Multi-functional duct sensor for monitoring and control of heating, ventilation and air-conditioning systems
This bus capable and calibratable pressure measuring transducer enables the control of differential...
more
Good room climate is measurable! - AERASGARD® FSCO2 ⁄ FSTM-CO2 ⁄ FSFTM-CO2-Modbus
Our multifunctional room sensors for measuring temperature, humidity and CO2 concentration can now...
more
ISH | 11. - 15.03.2019 | Stand 10.3 A71
more