Efficient, convenient and network-enabled
Elegant appearance, touch-operated interface, large display, and Modbus-compatible
RYMaskon
Patented quality product (Immersion sensor patent no. DE 10 2012 017 500.0)
Calibratable temperature measuring transducer THERMASGARD® TM 43 with eight switchable
measuring ranges, continuous linear output, straight protective tube, enclosure made from
impact-resistant plastic with snap-on lid.
For the detection of temperatures in liquid or gaseous media. For aggressive media, stainless steel
immersion sleeves must be used. It is used e.g. in piping systems, in heating technology, in storage
tanks, in district heating compact stations, in hot-water and cold-water systems, in oil and lubricant
circulation systems, in mechanical, apparatus and plant engineering as well as in the entire industrial
sector. These temperature measuring transducers are factory-calibrated.
Adjustment ⁄ fine adjustment by the user is possible (zero point offset is adjustable).
Voltage supply |
15...36 V DC depending on working resistance, residual ripple stabilised ± 0.3 V |
---|---|
Power consumption |
< 1,0 VA ⁄ 24 V DC
< 2,2 VA ⁄ 24 V AC |
Working resistance | Ra (ohm) = (Ub -14 V) ⁄ 0.02 A for I variant |
Temperature deviation | typically ± 0.2 K at +25 °C |
Output | 4...20 mA |
Sensor |
Pt1000, DIN EN 60751, class B (Perfect Sensor Protection) |
Connection type | 2- or 3-wire connection |
Measuring ranges |
multi-range switching with 8 switchable measuring ranges, see table (other ranges optional) with manual zero point correction (± 10 K) |
Ambient temperature | Measuring transducer –30...+70 °C |
Protective tube | stainless steel, 1.4571, V4A, Ø = 6 mm |
Electrical connection |
0.14 - 1.5 mm² via terminal screws on circuit board |
Enclosure |
plastic, UV-stabilised, material polyamide, 30 % glass-globe-reinforced colour traffic white (similar to RAL 9016) ALTF 02 with snap-on lid, |
Enclosure dimensions | 72 x 64 x 37.8 mm (Tyr 01) |
Cable gland |
2x M 12 x 1.5 (Y-adapter); with strain relief, exchangeable, max. inner diameter 6 mm |
Permissible air humidity | < 95 % r. H., non-precipitating air |
Protection class | III (according to EN 60 730) |
Protection type | IP 43 (according to EN 60 529) |
Standards |
CE conformity, electromagnetic compatibility according to EN 61326, according to EMC Directive 2014 ⁄ 30 ⁄ EU |
Type | Item No. | Price | |||
---|---|---|---|---|---|
MF-15-K | Mounting flange, plastic | 7100-0032-0000-000 | 5,16 € | ||
TH08-VA 100MM | Immersion sleeves, Stainless steel | 7100-0012-0020-132 | 18,90 € | ||
WLP-1 | Heat-conductive paste | Silicone-free heat-conductive paste | 7100-0060-1000-000 | 2,85 € | |
TH08-MS 100MM | Immersion sleeves, Brass | 7100-0011-0020-132 | 8,95 € |
ISH Messe Frankfurt – S+S Regeltechnik looks forward to meeting you!
11. - 15.03.2019
Stand 10.3 A71
At the ISH, the world's leading trade fair for "The Bathroom Experience,...
more
Multi-functional duct sensor for monitoring and control of heating, ventilation and air-conditioning systems
This bus capable and calibratable pressure measuring transducer enables the control of differential...
more
Good room climate is measurable! - AERASGARD® FSCO2 ⁄ FSTM-CO2 ⁄ FSFTM-CO2-Modbus
Our multifunctional room sensors for measuring temperature, humidity and CO2 concentration can now...
more
ISH | 11. - 15.03.2019 | Stand 10.3 A71
more