- New
- Sale
- Temperature
- Humidity
- Pressure
- Light Intensity & Motion
- Air Quality
- Flow
- Modbus | Wireless Modbus
- Room controller
- EtherCAT P
- Accessory
Description
Surface contact temperature/ tube contact temperature measuring transducers
THERMASGARD® ALTM1 - Modbus - T3
Technical details
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Measuring range, temperature
–50...+150 °C
Sensor
Pt1000, DIN EN 60751, class B
Measuring range
–50...+150 °C
Tmax up to +100 °C (compact variant)
Tmax up to +100 °C (compact variant)
Accuracy
typically ± 0.2 K at +25 °C
Zero point offset
± 10 °C
Ambient temperature
Measuring transducer –30...+70 °C
Error detection
sensor breakage, sensor short circuit
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
address range 0...247 selectable
Signal filtering
0,3 s / 1 s / 10 s
Process connection
endless metal strap and metal tightener
(included in scope of delivery)
(included in scope of delivery)
Strap dimensions
Ø = 13 - 92 mm (¼ - 3"), L = 300 mm
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Cable connection
cable gland, plastic
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Internal diagnostics
Error 1 at sensor breakage
Error 2 at sensor short circuit
Error 2 at sensor short circuit