Description
Sleeve sensor with temperature measuring transducer
THERMASGARD® HFTM - EtherCAT P
Interconnective THERMASGARD® HFTM - EtherCAT P sleeve temperature measuring transducer with M8 plug-in connector (EtherCATP-encoded), Bluetooth-enabled, in an impact resistant plastic housing with quick-locking screws, optionally with/without display and bar graph, cable sensor with stainless steel sleeve.
The sleeve sensor device serves to detect the temperature in liquid and gaseous media. It is used as a duct sensor or, if installed in a THE thermowell (accessory), as an immersion and screw-in sensor in liquids. The sensor is factory-calibrated.
The sleeve sensor device serves to detect the temperature in liquid and gaseous media. It is used as a duct sensor or, if installed in a THE thermowell (accessory), as an immersion and screw-in sensor in liquids. The sensor is factory-calibrated.
EtherCATP-enabled measuring transducer for industrial requirements with maximum reliability: includes easy PLC integration using the device's ESI configuration file, diagnostics (such as communication failure counter), advanced setting options, access to historical data (min/max) and establishing the sensor's service interval. Optionally with large back-lit three-line display (customised programming in the 7-segment and dot-matrix ranges) and bar graph (7-digit, LEDs freely configurable) for graphical display, e.g. as a traffic light indicator.
Technical details
Voltage supply
24VDC via EtherCATP (US)
Power consumption
< 3 W
Radio technology
Bluetooth (LE)
Sensor
Pt1000, DIN EN 60751, class B (Perfect Sensor Protection at IP68)
Sensor protection
Sensor sleeve made from stainless steel V4A (1.4571), Ø = 6 mm,
nominal length (NL) = 50 mm (optional 30...400 mm)
nominal length (NL) = 50 mm (optional 30...400 mm)
Measuring range
–50...+150 °C; Tmax to +150 °C
Accuracy
typically ± 0.2 K at +25 °C
Ambient temperature
Measuring transducer –30...+70 °C
Medium
Clean air and non-aggressive, non-combustible gases;
liquids depending on selected immersion sleeve (accessory)
liquids depending on selected immersion sleeve (accessory)
Cable connection
M8 plug-in connector, EtherCATP-encoded
Dimensions
126 x 90 x 50 mm (Tyr 2)
sensor cable
Silicone, SiHF, 2 x 0,25 mm²; cable length (KL) = 1.5 m
(other lengths and jacket materials, e.g. PTFE or
glass fibre with steel mesh, available on request)
(other lengths and jacket materials, e.g. PTFE or
glass fibre with steel mesh, available on request)
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) sleeve humidity-tight (standard)
IP 68 (according to EN 60 529) sleeve water-tight (optional)
IP 54 (according to EN 60 529) housing / with glass fibre cable (optional)
IP 68 (according to EN 60 529) sleeve water-tight (optional)
IP 54 (according to EN 60 529) housing / with glass fibre cable (optional)
Standards
CE conformity, according to EMC Directive 2014/ 30/ EU,
according to RED 2014/ 53/ EU
according to RED 2014/ 53/ EU