- New
- Sale
- Temperature
- Humidity
- Pressure
- Light Intensity & Motion
- Air Quality
- Flow
- Modbus | Wireless Modbus
- Room controller
- EtherCAT P
- Accessory
Description
Sleeve sensor with temperature measuring transducer (cable temperature measuring transducer)
THERMASGARD® HFTM
Calibratable THERMASGARD® HFTM temperature measuring transducer with sleeve sensor with eight switchable measuring ranges, continuous output, housing made of impact resistant plastic with quick-release screws, optionally with/without display, with cable gland or M12 connector according to DIN EN 61076-2-101.
The temperature transmitter with remote sensor serves to detect temperatures in liquid and gaseous media, e.g. if installed in a thermowell or as a duct sensor. A direct, permanent use in liquids is possible in combination with our THE thermowells (accessory).The sensor is factory-calibrated and can be fine-tuned to ambient conditions by an expert.
Technical details
Power consumption
< 1,0 W/ 24 V DC
< 2,2 VA/ 24 V AC
< 2,2 VA/ 24 V AC
Deviation of humidity
typically ± 0.2 K at +25 °C
Sensor
Pt1000, DIN EN 60751, class B
Sensor protection
sensor sleeve, stainless steel V4A (1.4571), Ø = 6 mm,
nominal length NL = 50 mm (other dimensions optionally available)
cable entry stamped (optionally rolled)
nominal length NL = 50 mm (other dimensions optionally available)
cable entry stamped (optionally rolled)
Connection type
2- or 3-wire connection
Measuring ranges
multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
with manual zero point correction (± 10 K)
see table (other ranges optional)
with manual zero point correction (± 10 K)
Accuracy
typically ± 0.2 K at +25 °C
Ambient temperature
Measuring transducer –30...+70 °C
Insulating resistance
100 MΩ,
at +20 °C (500V DC)
at +20 °C (500V DC)
Sensor protection
stainless steel, 1.4571, V4A, Ø = 6 mm,
nominal length (NL) = 50 mm
(other dimensions optional)
cable entry stamped (optional rolled)
nominal length (NL) = 50 mm
(other dimensions optional)
cable entry stamped (optional rolled)
Electrical connection
0.14 - 1.5 mm²
via terminal screws on circuit board
via terminal screws on circuit board
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
M12 connector according to DIN EN 61076-2-101 (optional on request)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
max. inner diameter 10.4 mm
sensor cable
Silicone, SiHF, 2 x 0,25 mm²; cable length (KL) = 1.5 m
(other lengths and jacket materials, e.g. PTFE or
glass fibre with steel mesh, available on request)
(other lengths and jacket materials, e.g. PTFE or
glass fibre with steel mesh, available on request)
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type (sensor)
IP 65 (according to EN 60 529) sleeve humidity-tight (standard)
IP 68 (according to EN 60 529) sleeve water-tight (optional)
IP 54 (according to EN 60 529) with glass fibre cable (optional)
IP 68 (according to EN 60 529) sleeve water-tight (optional)
IP 54 (according to EN 60 529) with glass fibre cable (optional)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU