Showcase humidity and temperature sensor VFTF - Modbus - T3
temperature Temperature
temperature Luftfeuchtigkeit

Showcase humidity and temperature sensor HYGRASGARD® VFTF-Modbus-T3

Product group: WG01

Low availability.

Usually ships in 3 to 5 days
556,65 €
662,41 € incl. VAT + shipping
+

Description

Showcase humidity and temperature sensor HYGRASGARD® VFTF - Modbus - T3
Calibratable display cases humidity and temperature sensor HYGRASGARD® VFTF - Modbus - T3, with Modbus connection, in an impact-resistant plastic housing with quick-locking screws, optionally with/ without display, cable sensor with a flat stainless steel probe (pluggable), to exactly detect the relative humidity (0…100% RH) and the temperature (–35...+80 °C) and to detect various parameters in humidity measurement. International system of units SI (default) can be switched to Imperial (via Modbus).

The display cases sensor is applied in a non-aggressive, dust-free environment and is specially suitable for installation in ceilings, walls, display cases or showcases. It is used in museums, galleries, cinemas, lecture halls or laboratories.

A long-term stable, digital humidity and temperature sensor guarantee exact measurement results. These measurands are used to internally calculate the following parameters that can be retrieved via Modbus: relative humidity, absolute humidity, mixture ratio, dew point, enthalpy (ignoring atmospheric air pressure) and ambient temperature.
Innovative Modbus sensor with galvanically separated RS485-Modbus-interface, selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in curent-free state, internal LEDs for telegram status display, two separate push-in terminals and large three-line display (illuminated; with customised programming in the 7-segment and dot-matrix range). The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

Technical details

Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Data points
Temperature [°C], relative humidity [% RH],
dew point [°C], absolute humidity [g / m3],
mixture ratio [g / kg], enthalpy [kJ / kg]
Deviation of humidity
typical ± 2.0 % (20…80 % RH); at + 25 °C, otherwise ± 3.0 %

Temperature deviation
typically ± 0.2 K at +25 °C
Sensor
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
Sensor protection
probe made of stainless steel, V4A (1.4571), pluggable;
sensor head Ø = 17 mm, H = approx. 2.5 mm;
protective sleeve Ø = 10 mm, NL = approx. 25 mm, M10 x 1.0;
with plastic plug connector Ø = approx. 11 mm,
NL = approx. 25 mm,
Measuring range
0...100 % RH (humidity)
-35...+80 °C (temperature)
Zero point offset
± 10 % RH (humidity)
± 5 °C (temperature)
Ambient temperature
–30...+70 °C
Medium
clean air and
non-aggressive, non-combustible gases
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
4 s / 32 s
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Cable connection
cable gland, plastic
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Cable gland
2x M 20 x 1.5; with strain relief, replaceable,
inner diameter 8 - 13mm
sensor cable
PVC, LiYY, 4 x 0.14 mm²,
KL = approx. 2 m
Mounting (sensor)
cut-out Ø = 11 - 15 mm, IL = approx. 50 mm,
lock nut for fixing is included in the scope of delivery.
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*