Description
Showcase humidity and temperature sensor
HYGRASGARD® VFF / VFTF
The calibratable HYGRASGARD® VFF / VFTF humidity and temperature transmitter measures the relative humidity and temperature of air. It converts the measurands of humidity and temperature into a standard signal of 0-10 V or 4...20 mA, and is available with/without an optional display. The sensor device supports four switchable temperature ranges. Relative humidity (in % r.H.) is the quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature.
The measuring transducer provides precise detection of temperature and humidity. A digital, long-term stable sensor is used as a measuring element for humidity and temperature. The sensor is factory-calibrated and can be fine-tuned to ambient conditions by an expert.
The measuring transducer provides precise detection of temperature and humidity. A digital, long-term stable sensor is used as a measuring element for humidity and temperature. The sensor is factory-calibrated and can be fine-tuned to ambient conditions by an expert.
The showcase sensor device is used in non-aggressive, dust-free environments and is specifically designed for installation in ceilings and walls as well as inside showcases or display cabinets in museums, galleries, cinemas, auditoriums or laboratories. The measuring element is contained inside a stainless steel probe, and its low height (approx. 2.5 mm) makes it barely noticeable.
Technical details
Measuring range, humidity
0...100 % RH
Operating range, humidity
0...95 % RH (without dew formation)
Deviation of humidity
typical ± 2.0 % (20…80 % RH); at + 25 °C, otherwise ± 3.0 %
Sensor protection
probe made of stainless steel, V4A (1.4571), pluggable;
sensor head Ø = 17 mm, H = approx. 2.5 mm;
protective sleeve Ø = 10 mm, NL = approx. 25 mm, M10 x 1.0;
with plastic plug connector Ø = approx. 11 mm,
NL = approx. 25 mm,
sensor head Ø = 17 mm, H = approx. 2.5 mm;
protective sleeve Ø = 10 mm, NL = approx. 25 mm, M10 x 1.0;
with plastic plug connector Ø = approx. 11 mm,
NL = approx. 25 mm,
Current consumption
max. 10 mA at 24 V DC
Ambient temperature
storage –5...+60 °C
operation –5...+60 °C
operation –5...+60 °C
Connection cable
PVC, LiYY, 4 x 0.14 mm²,
KL = approx. 2 m
KL = approx. 2 m
Electrical connection
2-, 3- or 4-wire connection
0.14 -1.5 mm ² via terminal screws on circuit board
0.14 -1.5 mm ² via terminal screws on circuit board
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
M12 connector according to DIN EN 61076-2-101 (optional on request)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
max. inner diameter 10.4 mm
sensor cable
PVC, LiYY, 4 x 0.14 mm²,
KL = approx. 2 m
KL = approx. 2 m
Long-term stability
± 1 % per year
Mounting (sensor)
cut-out Ø = 11 - 15 mm, IL = approx. 50 mm,
lock nut for fixing is included in the scope of delivery.
lock nut for fixing is included in the scope of delivery.
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) Housing tested,
TÜV SÜD, Report No.713139052 (Tyr 1)
TÜV SÜD, Report No.713139052 (Tyr 1)
Standards
CE conformity,
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3