ALTM1-SD-U

THERMASGARD® ALTM1-SD-U

Item No. 1101-6141-0219-920
EAN 4 251325 615745

Calibratable surface-contact temperature measuring transducer (compact variant) THERMASGARD® ALTM 1 with eight switchable measuring ranges, continuous output, in an impact-resistant plastic housing with quick-locking screws, optionally with/ without display, incl. strap.

The surface-contact sensor is used to detect the temperature on lines, pipes (e.g., cold and warm water) or on heating sections for heating control. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

72,78 € net
Voltage supply 24 V AC/ DC (± 10 %)
Power consumption < 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Temperature deviation typically ± 0.2 K at +25 °C
Sensor Pt1000, DIN EN 60751, class B
Connection type 2- or 3-wire connection
Measuring ranges multi-range switching with 8 switchable measuring ranges,
(other ranges optional)
compact variant: Tmax up to 100 °C, operating range –50...+100 °C
with manual zero point correction (± 10 K)
Ambient temperature Measuring transducer –30...+70 °C
Process connection endless metal strap and metal tightener
(included in scope of delivery)
Insulating resistance ≥ 100 MΩ,
at +20 °C (500V DC)
Strap dimensions Ø = 13 - 92 mm (¼ - 3"), L = 300 mm
Electrical connection 0.14 - 1.5 mm² via terminal screws
Cable connection cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing plastic, UV-stabilised,
material polyamide, 30 % glass-globe-reinforced
colour traffic white (similar to RAL 9016)
ALTF 02 with snap-on lid,
Cable gland M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Permissible air humidity < 95 % r. H., non-precipitating air
Protection class III (according to EN 60 730)
Protection type IP 43 (according to EN 60 529)
Standards CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU