RPTM1-U LCD

THERMASGARD® RPTM1-U DISPLAY

Item No. 1101-1161-2219-910
EAN 4 251325 600710

Calibratable resistance thermometer THERMASGARD® RPTM 1 with eight switchable RPTM 1 measuring ranges, continuous output, without/ with optional display (for indicating the actual temperature), with terminal box housing made of impact-resistant plastic, housing cover with quick-locking screws. The pendulum room temperature sensor is specifically designed for temperature detection in larger rooms or halls. Due to the measuring method employed by this pendulum room temperature sensor in combination with its positioning in the room, an excellent measuring result that is representative of the room is achieved thanks to the uniform flow of ambient air around the sensor. The temperature transmitters are factory-calibrated. Adjustment/ fine adjustment by the user is possible (zero point offset is adjustable).

165,51 € net
Voltage supply 24 V AC/ DC (± 10 %)
Power consumption < 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Load resistance RL > 5 kOhm
Temperature deviation typically ± 0.2 K at +25 °C
Output 0 - 10 V
Sensor Pt1000, DIN EN 60751, class B
Connection type 2- or 3-wire connection
Measuring ranges multi-range switching with 8 switchable measuring ranges
(other ranges optional) Tmin –5 °C, Tmax +60 °C
with manual zero point correction (± 10 K)
Ambient temperature measuring transducer –5...+60 °C
Connection cable PVC; LiYY, 1.5 m
(other lengths optional: e.g. 3 m, 6 m)
Protective tube stainless steelV2A (1.4301), Ø = 16 mm, L = 142 mm
Electrical connection 0.14 - 1.5 mm² via terminal screws
Housing plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Housing dimensions 72 x 64 x 43.3 mm (Tyr 1 with Display)
Cable gland M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Connection cable PVC, H03VV-F, 2 x 0.5 mm2,
KL = approx. 1.5 m (other lengths optional)
Humidity < 95 % r. H., non-precipitating air
Protection class III (according to EN 60 730)
Protection type IP 65 (according to EN 60 529)
Standards CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Display Display mit Beleuchtung, zweizeilig,
Ausschnitt ca. 36 x15 mm (B x H),
zur Anzeige der Ist -Temperatur
und der Eigendiagnostik
(Messbereichsüberschreitung,
Messbereichsunterschreitung,
Fühlerbruch, Fühlerkurzschluss)