RPTM1-U LCD

THERMASGARD® RPTM1-U LCD

Item No. 1101-1161-2219-910
EAN 4 251325 600710

Calibratable room pendulum temperature measuring transducer (with sleeve) THERMASGARD® RPTM 1 with eight switchable measuring ranges, continuous output, in an impact-resistant plastic housing with quick-locking screws, optionally with/ without display, cable sensor with stainless steel sleeve and plastic sinter filter (exchangeable).

The pendulum sensor has been specially designed to detect the temperature in larger rooms or halls. The resistance thermometer achieves a very good representative measurement result due to its positioning in the room. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

170,02 € net
Voltage supply 24 V AC/ DC (± 10 %)
Power consumption < 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Load resistance RL > 5 kOhm
Temperature deviation typically ± 0.2 K at +25 °C
Output 0 - 10 V
Sensor Pt1000, DIN EN 60751, class B
Connection type 2- or 3-wire connection
Measuring ranges multi-range switching with 8 switchable measuring ranges
(other ranges optional) Tmin –5 °C, Tmax +60 °C
with manual zero point correction (± 10 K)
Ambient temperature measuring transducer –5...+60 °C
Connection cable PVC; LiYY, 1.5 m
(other lengths optional: e.g. 3 m, 6 m)
Protective tube stainless steelV2A (1.4301), Ø = 16 mm, L = 142 mm
Electrical connection 0.14 - 1.5 mm² via terminal screws
Cable connection cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Housing dimensions 72 x 64 x 43.3 mm (Tyr 1 with Display)
Cable gland M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Connection cable PVC, H03VV-F, 2 x 0.5 mm2,
KL = approx. 1.5 m (other lengths optional)
Humidity < 95 % r. H., non-precipitating air
Protection class III (according to EN 60 730)
Protection type IP 65 (according to EN 60 529)
Standards CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Display display with illumination, two-line, cut-out approx. 36 x15 mm (B x H),
to display the actual temperature and internal diagnostics
(measuring range exceeded, measuring range not reached,
sensor breakage, sensor short circuit)