ATM2-SD-I

THERMASGARD® ATM2-SD-I

Item No. 1101-1192-0009-900
EAN 4 251325 615967

Calibratable outside temperature measuring transducer THERMASGARD® ATM 2 with eight switchable measuring ranges, internal or remote sensor, continuous output, terminal box housing made of impact- resistant plastic, housing cover with quick-locking screws, with or without optional display. For the detection of outside temperatures, temperatures in wet room areas, e.g. for installation on outside walls, in cold storage buildings and greenhouses, in the industrial sector and in agriculture. Installation in outdoor areas preferably at the north side of a building or in a protected place. In cases of direct solar irradiation, we recommend the use of our WS 01 or WS 04 sun protection hood (accessory) or the device version with installed sun protection hood SS 02 (available upon request). The sensor is factorycalibrated; an environmental precision adjustment by an expert is possible.

76,88 € net
Voltage supply 15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Power consumption < 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Temperature deviation typically ± 0.2 K at +25 °C
Sensor Pt1000
Connection type 2- or 3-wire connection
Measuring ranges multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
operating range –30...+70 °C
with manual zero point correction (± 10 K)
Ambient temperature Measuring transducer –30...+70 °C
Process connection by screws
Electrical connection 0.14 - 1.5 mm² via terminal screws
Cable connection cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing plastic, UV-stabilised,
material polyamide, 30 % glass-globe-reinforced
colour traffic white (similar to RAL 9016)
ALTF 02 with snap-on lid,
Housing dimensions 72 x 64 x 37.8 mm (Tyr 01)
Cable gland M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Permissible air humidity < 95 % r. H., non-precipitating air
Protection class III (according to EN 60 730)
Protection type IP 43 (according to EN 60 529)
Standards CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU