ATM2-SD-I

THERMASGARD® ATM2-SD-I

Item No. 1101-1192-0009-900
EAN 4 251325 615967

Calibratable outside temperature measuring transducers THERMASGARD® ATM 2 with eight switchable measuring ranges, internal or remote sensor, continuous output, with housing made of impact-resistant plastic and fitted with quick-locking screws, with/ without optional display. It is used to detect outside temperatures, temperatures in wet rooms e.g. for installation on outside walls, in cold storage buildings and greenhouses, in the industrial sector and in agriculture. Installation in outdoor areas preferably at the north side of a building or in a protected place.
In case of direct sun irradiation, the sunshade and ball game protection WS 01 or WS 04 (accessories) or the device variant with the installed sunshade SS 02 (available on request) must be used. The outdoor sensors are factory-calibrated. Adjustment/ fine adjustment by the user is possible (zero point offset is adjustable).

75,00 € net
Voltage supply 15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Power consumption < 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Temperature deviation typically ± 0.2 K at +25 °C
Sensor Pt1000
Connection type 2- or 3-wire connection
Measuring ranges multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
operating range –30...+70 °C
with manual zero point correction (± 10 K)
Ambient temperature Measuring transducer –30...+70 °C
Process connection by screws
Electrical connection 0.14 - 1.5 mm² via terminal screws
Housing plastic, UV-stabilised,
material polyamide, 30 % glass-globe-reinforced
colour traffic white (similar to RAL 9016)
ALTF 02 with snap-on lid,
Housing dimensions 72 x 64 x 37.8 mm (Tyr 01)
Cable gland M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Permissible air humidity < 95 % r. H., non-precipitating air
Protection class III (according to EN 60 730)
Protection type IP 43 (according to EN 60 529)
Standards CE conformity,
electromagnetic compatibility according to EN 61326,