KCO2 MODBUS

AERASGARD® KCO2 MODBUS

Item No. 1501-8110-6001-200
EAN 4 251325 611709

326,40 € net
Voltage supply 24 V AC/ DC (± 10 %)
Power consumption < 4.4 W/ 24 V DC typical; < 6.4 VA/ 24 V AC typical;
peak current 200 mA
Data points temperature, relative humidity,
air quality (VOC), carbon dioxide (CO2),
atmospheric pressure
Measuring range, CO2 0...5000 ppm
Sensor, CO2 optical NDIR sensor (non-dispersive infra-red technology)
including atmospheric pressure compensation (up to 1100 mbar)
with automatic and manual calibration
Measuring accuracy, CO2 typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2 ± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence ± 0,13 %/ mm Hg
Gas exchange by diffusion
Response time < 2 minutes
Ambient temperature –10...+60 °C
Bus protocol Modbus (RTU mode),
address range 0...247 selectable
Signal filtering 4 s / 32 s
Process connection by mounting flange, plastic
(included in the scope of delivery)
Protective tube PLEUROFORMTM, material polyamide (PA6), with torsion protection, Ø 20 mm, vmax = 30 m/s (air)
without filter: NL = 202.5 mm / with plastic filter: NL = 235 mm (optional with metal filter: NL = 227 mm)
Electrical connection 0.14 - 1.5 mm2, via push-in terminal
Housing plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Housing dimensions 126 x 90 x 50 mm (Tyr 2)
Cable gland 2x M 16 x 1.5; including strain relief, exchangeable
Long-term stability < 2 % in 15 years
Protection class III (according to EN 60 730)
Protection type IP 65 (according to EN 60 529) housing only! (PLEUROFORM IP 30)
Standards

CE-Konformitat, elektromagnetische
Vertraglichkeit nach EN 61326,
nach EMV-Richtlinie 2014/ 30/ EU

Type Item No. Price
KA-2 1906-1200-0000-100 0,00 €