HFTM-MODBUS LCD

THERMASGARD® HFTM-MODBUS

Item No. 1101-1256-2210-000
EAN 4 251325 600857

calibratable temperature measuring transducer with sleeve sensor THERMASGARD® HFTM - Modbus with Modbus connection, terminal box housing made of impact-resistant plastic, housing cover with quick-locking screws, with/ without optional display indicating the actual temperature.
The temperature transmitter with remote sensor is used to detect temperatures in liquid and gaseous media e.g. if installed in an immersion sleeve or as a duct sensor. The sensors are factory-calibrated. Adjustment/ fine adjustment by the user is possible (zero point offset is adjustable).

151,51 € net
Voltage supply 24 V AC (± 20 %) and
15…36 V DC
Power consumption < 1,0 VA/ 24 V DC
< 2,2 VA/ 24 V AC
Temperature deviation typically ± 0.2 K at +25 °C
Sensor Pt1000, DIN EN 60751, class B
Measuring range –50...+150 °C
Zero point offset ± 10 °C
Ambient temperature Measuring transducer –30...+70 °C
Medium clean air and
non-aggressive, non-combustible gases
Error detection sensor breakage, sensor short circuit
Bus protocol Modbus (RTU mode),
address range 0...247 selectable
Signal filtering 0,3 s / 1 s / 10 s
Protective tube (sensor sleeve) stainless steel, 1.4571, V4A, Ø = 6 mm,
nominal length (NL) = 50 mm
(other dimensions optional)
cable entry stamped (optional rolled)
Connection cable silicone, SiHF, 2 x 0.25 mm², KL = 1.5 m
(other lengths and range limits optional,
e.g. PTFE leads up to + 250 °C or
glass fibre with steel wire mesh up to + 350°C)
Housing plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Housing dimensions 72 x 64 x 43.3 mm (Tyr 1 with Display)
Cable gland 2x M 12 x 1.5 (Y-adapter); with strain relief,
exchangeable, max. inner diameter 6 mm
Permissible air humidity < 95 % r. H., non-precipitating air
Protection class III (according to EN 60 730)
Protection type IP 65 (according to EN 60 529) humidity-tight stamped
IP 68 (optional watertight compound-filled) rolled
IP 54 (optional glass fibre cable)
Standards CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Display two-line display with illumination, programmable,
cutout approx. 36 x 15 mm (W x H),
for displaying the actual temperature or
an individually programmable display value
(The Modbus interface allows the display to be individually
configured in the 7-segment area and in the dot-matrix area.)
Type Item No. Price
KA-2 1906-1200-0000-100 0,00 €
MODBUS-Y Y-adapter Y-adapter as bypass for bus connection 7000-0005-0002-100 8,88 €