RPFTF-I

HYGRASGARD® RPFTF-I

Item No. 1201-1172-1000-100
EAN 4 251325 610122

The calibratable pendulum room humidity and temperature sensor HYGRASGARD® RPFF/ RPFTF with plastic sinter filter measures the relative humidity and temperature of air. It converts the measurands into standard signals of 0 - 10 V or 4...20 mA and is available with or without an optional display. It has four switchable temperature ranges. The sensor is applied in non-aggressive dust-free atmospheres in refrigeration, air conditioning, ventilation and clean room technology, hotels, technical rooms, meeting rooms and convention centres. These measuring transducers are designed for exact detection of temperature and humidity. A digital long-term stable sensor is used as a measuring element for humidity and temperature measurement. The sensor is appropriate for ceiling and duct installation, or for integrating it into equipment. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

175,54 € net
Voltage supply 15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
Power consumption < 1.1 VA/ 24 V DC ; < 2.2 VA/ 24 V AC
Working resistance Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant
Sensors digital humidity sensor
with integrated temperature sensor,

low hysteresis, high long-term stability
Measuring range, humidity 0...100 % r. H.
(output corresponding to 4...20 mA)
Operating range, humidity 0...95 % r. H. (without dew formation)
Deviation of humidity typical ± 2 % r. H. (20…80 % r. H. ); at + 25 °C, otherwise ± 3 %
Output, humidity 4...20 mA
Measuring range, temperature multi-range switching
with 4 switchable measuring ranges

–35...+35 °C; –35...+75 °C; 0...+50 °C; 0...+80 °C
(output corresponding to 0 -10 V or 4...20 mA)
Operating range, temperature –35...+80 °C
Temperature deviation typically ± 0.2 K at +25 °C
Output, temperature 4...20 mA
Sensor protection plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
Ambient temperature storage –5...+60 °C
operation –5...+60 °C
Protective tube stainless steelV2A (1.4301), Ø = 16 mm, L = 142 mm
Electrical connection 2-, 3- or 4-wire connection
0.14 -1.5 mm ² via terminal screws on circuit board
Cable connection cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Housing dimensions 72 x 64 x 37,8 mm (Tyr 1)
Cable gland M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Connection cable PVC, LiYY, 6 x 0.14 mm2,
KL = approx. 2 m (other lengths optional)
Long-term stability ± 1 %/ year
Protection class III (according to EN 60 730)