Leakage sensor/ water ingress detector with switching output LS-2
temperature Luftfeuchtigkeit + berechnete Werte

Leakage sensor/ water ingress detector with switching output HYGRASREG® LS-2

Item no. 1202-1042-0000-000
EAN 4251325611549
Product group: WG01

In Stock

Usually ships in 1 to 3 days
107,34 €
127,73 € incl. VAT + shipping
+

Description

Leakage sensor/ water ingress detector with switching output HYGRASREG® LS
The HYGRASREG® LS leakage / water ingress detector with leakage location serves to detect ingress of water and conductive liquids. It has been designed for early water leakage detection to protect sensitive electrical and electronic equipment in buildings against humidity.
The water ingress detector consists of an electronic monitoring system and a matching electrode which can be extended by the user.

Technical details

Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Monitoring range
conductive liquids between the probes
Switching threshold
conductance between electrodes > threshold
Power consumption
< 1,0 W/ 24 V DC
< 2,2 VA/ 24 V AC
Output
changeover contact
Output signal
potential-free changeover contact (24 V), 1 A ohmic load
Electrical connection
0.14 - 1.5 mm² via terminal screws
Housing dimensions
72 x 64 x 43.3 mm (Tyr 1 with Display)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Process connection
two external probes, laid according to measuring task (on the LS - 2)
or upright on four electrodes with insulating plastic caps
, which are mounted on the housing underside (on the LS - 4)
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Function
The leak sensor can be set using DIP switches so that
the relay is energised during normal operation.
This means that relay opens in the event of a fault
(water damage, cable breakage, power failure).
This also enables a break in the cable to the sensor to be detected.