Room CO2 and temperature sensor or measuring transducer FSTM-CO2-U
temperature CO2
temperature Temperature
temperature Luftfeuchtigkeit

Room CO2 and temperature sensor or measuring transducer AERASGARD® FSTM-CO2-U

Item no. 1501-9122-1001-162
EAN 4251325617305
Product group: WG02

In Stock

Usually ships in 1 to 3 days
352,92 €
419,97 € incl. VAT + shipping
+

Description

Room CO2 and temperature sensor or measuring transducer AERASGARD® FSCO2/FSTM-CO2
The AERASGARD® FSCO2 / FSTM - CO2 room climate transmitter with in-wall housing is used for measuring The CO2 content and temperature of the air. It converts the measured values into a standard signal of 0-10 V.

The CO2 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). A digital, long-term stable sensor is used for temperature measurement.

The in-wall measuring transducer is mounted either individually or in combination with light switches, socket outlets, etc. in high-quality panel switch brand programmes, such as preferably from Gira, Berker, Merten, Jung, Siemens or Busch-Jaeger (with in-wall adapters).
It is used in non-aggressive, dust-free environments, in refrigeration, air conditioning and cleanroom engineering, and in interior spaces, such as living rooms, offices, hotels, etc.

Technical details

Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 1.5 VA/ 24 V DC, < 2.8 VA/ 24 V AC
Data points
temperature, carbon dioxide (CO2)
Measuring range, temperature
0...+50 °C
Temperature deviation
typically ± 0.8 K at +25 °C
Output, temperature
0 - 10 V
Warm up time
approx. 1 hour
Response time
< 2 minutes
Protection class
III (according to EN 60 730)
Protection type
IP 20 (according to EN 60 529)
Protection type housing
IP 20
Sensor, CO2
optical NDIR sensor
(non-dispersive infra-red technology),
with manual calibration (via zero button) and
automatic calibration (fixed)
Output, CO2
0 - 10 V
Measuring accuracy, CO2
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Sensor
digital temperature sensor,
low hysteresis, high long-term stability
Measuring range
0...2000 ppm
Ambient temperature
storage –35...+85 °C;
operation 0...+50 °C
Medium
clean air and
non-aggressive, non-combustible gases
Electrical connection
0.14 - 1.5 mm², using plug terminals
Housing
plastic, colour pure white glossy (similar to RAL 9010)
(other colours are possible on request with colour variants
depending on the respective switch programme)
Installation
in in-wall flush box Ø 55 mm
Long-term stability
< 2 % in 15 years

± 1 % per year
Permissible air humidity
max. 90 % RH, non-precipitating air
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Manufacturer
GIRA System 55 Standard
(other switch programmes, manufacturers, colours
and prices upon request