ACO2-SD-U

AERASGARD® ACO2-SD-U

Item No. 1501-7110-1001-200
EAN 4 251325 616353

Maintenance-free on-wall sensor AERASGARD® ACO2-SD with active output, automatic calibration (fixed), in an impact-resistant plastic housing with quick-locking screws, for determining the CO2 content of the air (0…2000 ppm/0...5000 ppm). The measuring transducer converts the measured values into a standard signal of 0 -10 V.

Maintenance-free on-wall sensor AERASGARD® ACO2-W with active/switching output, automatic calibration (can be deactivated), in an impact-resistant plastic housing with quick-locking screws, optionally with/without display, for determining the CO2 content of the air (0…2000 ppm/0...5000 ppm). he measuring transducer converts the measured values into a standard signal of 0 -10 V or 4...20 mA (switchable).

The sensor is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.

The CO2 measurement is performed using an optical NDIR sensor (non-dispersive infra-red technology). The detection range is calibrated for standard applications such as monitoring residential rooms and conference rooms.

221,65 € net
Voltage supply 24 V AC/ DC (± 10 %)
Power consumption < 1.5 W/ 24 V DC typical;
< 2.9 VA/ 24 V AC typical;
peak current 200 mA
Measuring range, CO2 multi-range switching (selectable via DIP switches)
0...2000 ppm; 0...5000 ppm
Measuring accuracy, CO2 typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2 ± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence ± 0,13 %/ mm Hg
Gas exchange by diffusion
Relay output without changeover contact
Warm up time approx. 1 hour
Response time approx. 1 minute
Output 0 -10 V (fixed)
Output 0 -10 V or 4...20 mA (selectable via DIP switches,
selected variant applies for all outputs), working resistance < 800 Ω
Sensor optical NDIR sensor
(non-dispersive infra-red technology),
with manual calibration (via zero button) and
automatic calibration (fixed)
Ambient temperature –10...+60 °C
Process connection by screws
Protective tube stainless steel V2A (1.4301), Ø 16 mm, NL = 55 mm
Electrical connection 0.14 - 1.5 mm² via terminal screws
Cable connection cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Housing dimensions 126 x 90 x 50 mm (Tyr 2)
Cable gland M 16 x 1.5; including strain relief,
exchangeable
Long-term stability < 2 % in 15 years
Protection class III (according to EN 60 730)
Protection type IP 65 (according to EN 60 529)
Standards CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Type Item No. Price