RCO2-W LCD

AERASGARD® RCO2-W-DISPLAY

Item No. 1501-61B0-7321-200
EAN 4 251325 613130

The maintenance-free microprocessor-controlled room sensor AERASGARD® RCO2 - SD with automatic calibration (fixed) is used for recording the CO2 content of the air within a range of 0...2000 ppm. The measurement value is converted into standard signal of 0 -10 V.

The maintenance-free microprocessor-controlled room sensor AERASGARD® RCO2 - W with automatic calibration (can be deactivated via DIP switches) is used for detecting the CO2 content of the air within a range of 0...2000 ppm or 0...5000 ppm. The measurement value is converted into standard signal of 0 -10 V or 4...20 mA. Optional with traffic light indicator (five coloured LEDs).

Elegant housing made of plastic, with snap-on lid, based with 4-hole attachment, for installation on vertically or horizontally installed flush-mounted boxes, with predetermined breaking point for surfacemounted connection or in housing made of stainless steel (top and bottom parts are stainless steel, the cover is screwed on), vandal-proof version e.g. for schools, barracks and public buildings.

The CO2 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detection range of the CO2 sensor is calibrated for standard applications such as monitoring residential rooms and conference rooms. Room ventilation on an as-needed basis, improved well-being and customer benefit, increased comfort as well as reduced operating costs through energy conservation.

261,33 € net
Voltage supply 24 V AC/ DC (± 10 %)
Power consumption < 1.5 W/ 24 V DC typical;
< 2.9 VA/ 24 V AC typical;
peak current 200 mA
Output, CO2 0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring accuracy typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2 ± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence ± 0,13 %/ mm Hg
Gas exchange by diffusion
Relay output with potential-free changeover contact 24 V (assignment selectable via DIP switches)
Warm up time approx. 1 hour
Response time < 2 minutes
Output 0 -10 V  or  4...20 mA,  working resistance  < 800  Ω
(selectable via DIP switches) 
with offset potentiometer (± 10 % of the measuring range
Sensor
Optical NDIR sensor (non-dispersive infra-red technology),
with manual calibration (via zero button), 
with automatic calibration (can be deactivated via DIP switches)
Measuring range 0...2000 ppm or 0...5000 ppm (selectable via DIP switches)
Ambient temperature 0...+50 °C
Electrical connection 0.14 - 1.5 mm² via terminal screws
Housing plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions 98 x 98 x 33 mm (Baldur 2)
Installation wall mounting or on in-wall flush box, Ø 55 mm,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation
Long-term stability < 2 % in 15 years
Protection class III (according to EN 60 730)
Protection type IP 30 (according to EN 60 529)
Standards CE conformity, electromagnetic compatibility
according to EN 61 326, EMC Directive 2014/ 30/ EU,
Low Voltage Directive 2014/ 35/ EU
Display with display for displaying the actual CO2 content in ppm