EAN 4 251325 613130

Maintenance-free room sensor AERASGARD® RCO2 - SD with active output, automatic calibration (fixed), in an elegant plastic housing with snap-on lid, for determining the CO2 content of the air (0...2000 ppm). The measuring transducer converts the measured values into a standard signal of 0 -10 V.

Maintenance-free room sensor AERASGARD® RCO2 - W with active/switching output, automatic calibration (can be deactivated), in an elegant plastic housing with snap-on lid, optional with traffic light indicator (five coloured LEDs), for determining the CO2 content of the air (0...2000 ppm/0...5000 ppm). The measuring transducer converts the measured values into a standard signal of 0 -10 V or 4...20 mA (switchable).

The sensor is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.

The CO2 measurement is performed using an optical NDIR sensor (non-dispersive infra-red technology). The detection range is calibrated for standard applications such as monitoring residential rooms and conference rooms.

267,86 € net
Voltage supply 24 V AC/ DC (± 10 %)
Power consumption < 1.5 W/ 24 V DC typical;
< 2.9 VA/ 24 V AC typical;
peak current 200 mA
Service life > 60 months (under normal load conditions)
depending on the type of loading and gas concentration
Output, CO2 0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring accuracy typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2 ± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence ± 0,13 %/ mm Hg
Gas exchange by diffusion
Relay output with potential-free changeover contact 24 V (assignment selectable via DIP switches)
Warm up time approx. 1 hour
Response time < 2 minutes
Output 0 -10 V  or  4...20 mA,  working resistance  < 800  Ω
(selectable via DIP switches) 
with offset potentiometer (± 10 % of the measuring range
Sensor
Optical NDIR sensor (non-dispersive infra-red technology),
with manual calibration (via zero button), 
with automatic calibration (can be deactivated via DIP switches)
Measuring range 0...2000 ppm or 0...5000 ppm (selectable via DIP switches)
Ambient temperature 0...+50 °C
Electrical connection 0.14 - 1.5 mm² via terminal screws
Housing plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions 98 x 98 x 33 mm (Baldur 2)
Installation wall mounting or on in-wall flush box, Ø 55 mm,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation
Long-term stability < 2 % in 15 years
Protection class III (according to EN 60 730)
Protection type IP 30 (according to EN 60 529)
Standards CE conformity, electromagnetic compatibility
according to EN 61 326, EMC Directive 2014/ 30/ EU,
Low Voltage Directive 2014/ 35/ EU
Display with display for displaying the actual CO2 content in ppm