- New
- Sale
- Temperature
- Humidity
- Pressure
- Light Intensity & Motion
- Air Quality
- Flow
- Modbus | Wireless Modbus
- Room controller
- EtherCAT P
- Accessory
Description
Pressure, differential pressure and volume flow measuring transducers
PREMASGARD® 212x-SD
The calibratable compact pressure transmitters of the PREMASGARD® 212x - SD series are equipped with 8 switchable measuring ranges, 2 switchable output signals (16 devices in one) and with or without optional display. They are used for measuring above-atmospheric, belowatmospheric, or differential pressures and volume flow in air. The piezoresistive measuring element is temperature-compensated and guarantees a high degree of reliability and accuracy.
These pressure measuring transducers have a pushbutton for manual zero-point calibration and an adjustable offset. Applications are found in cleanroom, medical and filter engineering, in ventilation and air conditioning ducts, in spray booths and large-scale catering facilities, in filter monitoring and level measuring or frequency converter triggering. Media measured with these pressure transducers are air (non-precipitating) or other gaseous, non-aggressive, non-combustible media. The differential pressure transmitters are supplied including our ASD-06 connection set (2 m connection hose, two pressure connection nipples, screws).
Technical details
Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 1 W at 24 V DC; < 2 VA at 24 V AC
Working resistance
Ra (Ohm) = 25 ...450 Ohm for I variant
Load resistance
RL > 25 kOhm for U variant
Output
switchable 0 -10 V/ 4...20 mA (via DIP switches)
Connection type
3-wire connection
Measuring function
Differential pressure, volume flow (square root output signal)
Current consumption
< 45 mA
Measuring ranges
multi-range switching with 8 switchable measuring ranges
Media temperature
–20...+50 °C (temperature-compensated 0...+50 °C)
Pressure connection
with connection nozzles for pressure hose Ø 6 mm
Type of pressure
differential pressure
Pressure range
±5000Pa
Zero point offset
± 5 % of final value
Above- below-pressure
± 50 kPa
Medium
clean air and
non-aggressive, non-combustible gases
non-aggressive, non-combustible gases
Signal filtering
switchable 1 s/ 10 s (via DIP switches)
Electrical connection
0.14 - 1.5 mm² via terminal screws
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
max. inner diameter 10.4 mm
Long-term stability
± 1 % per year
Hysteresis
0.3 % of final value
Media contacting parts
Brass, Ni, Duroplast, Si, epoxy, RTV, BSG, UV silicone gel
Temperature drift values
± 0.1 % of final value/ °C
Linearity
< ± 1 % of final value
Air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Accuracy
(5000 Pa): typically ± 35 Pa at +25 °C
compared to the calibrated reference device
compared to the calibrated reference device
Protection type
IP 54 (according to EN 60 529) Housing tested,
TÜV SÜD, Report No. 713160960A (Tyr 01)*
TÜV SÜD, Report No. 713160960A (Tyr 01)*
Accuracy, pressure
± 35 Pa
Measuring range pressure
0 ... +1000 Pa / -1000 ... +1000 Pa
0 ... +2000 Pa / -2000 ... +2000 Pa
0 ... +3000 Pa / -3000 ... +3000 Pa
0 ... +5000 Pa / -5000 ... +5000 Pa
0 ... +2000 Pa / -2000 ... +2000 Pa
0 ... +3000 Pa / -3000 ... +3000 Pa
0 ... +5000 Pa / -5000 ... +5000 Pa
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Housing dimensions
72 x 64 x 37.8 mm (Tyr 01)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU