Pendulum room temperature measuring transducer RPTM2 - Modbus - T3
temperature Temperature

Pendulum room temperature measuring transducer THERMASGARD® RPTM2-Modbus-T3

Product group: WG01

Low availability.

Usually ships in 3 to 5 days
271,12 €
227,83 € + VAT + shipping
+

Description

Pendulum room temperature measuring transducer THERMASGARD® RPTM2 - Modbus - T3
Calibratable room pendulum temperature measuring transducer (with sleeve) THERMASGARD® RPTM 1 - Modbus - T3, with Modbus connection, in an impact-resistant plastic housing with quick-locking screws, cable sensor with stainless steel sleeve and plastic sinter filter (exchangeable), optionally with/ without display, measures temperature (–50...+150 °C). International system of units SI (default) can be changed to imperial (via Modbus).
Calibratable room pendulum temperature measuring transducer (with globe) THERMASGARD® RPTM 2 - Modbus - T3, with Modbus connection, in an impact-resistant plastic housing with quick-locking screws, cable sensor with a black plastic globe, optionally with/ without display, measures temperature (–50...+150 °C). International system of units SI (default) can be changed to imperial (via Modbus).

The pendulum sensor has been specially designed to detect the temperature in larger rooms or halls. The resistance thermometer achieves a very good representative measurement result due to its positioning in the room.
Innovative Modbus sensor with galvanically separated RS485 Modbus interface, selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal LEDs for telegram status display, two separate push-in terminals and large three-line display (illuminated, with customised programming in the 7-segment range and dot-matrix range). Uses internal diagnostics to detect sensor breakage or sensor short circuit as errors. The error messages can be retrieved via Modbus and are shown on the display. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

Technical details

Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Measuring range, temperature
–50...+150 °C
Sensor
Pt1000, DIN EN 60751, class B
Measuring range
– 50...+ 150 °C; Tmin –50 °C, Tmax + 80 °C
Accuracy
typically ± 0.2 K at +25 °C
Zero point offset
± 10 °C
Ambient temperature
Measuring transducer –30...+70 °C
Medium
clean air and
non-aggressive, non-combustible gases
Error detection
sensor breakage, sensor short circuit
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
0,3 s / 1 s / 10 s
Globe
plastic, colour black, Ø = 50 mm
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Cable connection
cable gland, plastic
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Cable gland
2x M 20 x 1.5; with strain relief, replaceable,
inner diameter 8 - 13mm
sensor cable
PVC, H03VV-F, 2 x 0.5 mm²,
KL = approx. 1.5 m (other lengths optional)
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Units
switchable metric / imperial
Internal diagnostics
Error 1 at sensor breakage
Error 2 at sensor short circuit
Prices are now displayed including taxes