Efficient, convenient and network-enabled
Elegant appearance, touch-operated interface, large display, and Modbus-compatible
RYMaskon
calibratable outside temperature measuring transducer with internal or external sensor THERMASGARD® ATM 2 - Modbus with Modbus connection, terminal box enclosure made of impact-resistant plastic, enclosure cover with quick-locking screws, with ⁄ without optional display indicating the actual temperature.
It is used to detect outside temperatures, temperatures in wet rooms e.g. for installation on outside walls, in cold storage buildings and greenhouses, in the industrial sector and in agriculture. Installation in outdoor areas preferably at the north side of a building or in a protected place. In case of direct sun irradiation, the sunshade and ball game protection WS 01 or WS 04 (accessories) or the device variant with the installed sunshade SS 02 (available on request) must be used. The outdoor sensors are factory-calibrated. Adjustment ⁄ fine adjustment by the user is possible (zero point offset is adjustable).
Voltage supply |
24 V AC (± 20 %) and 15…36 V DC |
---|---|
Power consumption |
< 1,0 VA ⁄ 24 V DC
< 2,2 VA ⁄ 24 V AC |
Temperature deviation | typically ± 0.2 K at +25 °C |
Sensor | Pt1000, DIN EN 60751, class B |
Measuring range | –50...+150 °C |
Zero point offset | ± 10 °C |
Ambient temperature | Measuring transducer –30...+70 °C |
Medium |
clean air and non-aggressive, non-combustible gases |
Error detection | sensor breakage, sensor short circuit |
Bus protocol |
Modbus (RTU mode), address range 0...247 selectable |
Signal filtering | 0,3 s / 1 s / 10 s |
Process connection | by screws |
Enclosure |
plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced, with quick-locking screws (slotted ⁄ Phillips head - combination), colour traffic white (similar to RAL 9016) |
Enclosure dimensions | 72 x 64 x 37,8 mm (Tyr 1) |
Cable gland |
2x M 12 x 1.5 (Y-adapter); with strain relief, exchangeable, max. inner diameter 6 mm |
Permissible air humidity | < 95 % r. H., non-precipitating air |
Protection class | III (according to EN 60 730) |
Protection type | IP 65 (according to EN 60 529) |
Standards |
CE conformity, electromagnetic compatibility according to EN 61326, according to EMC Directive 2014 ⁄ 30 ⁄ EU |
ISH Messe Frankfurt – S+S Regeltechnik looks forward to meeting you!
11. - 15.03.2019
Stand 10.3 A71
At the ISH, the world's leading trade fair for "The Bathroom Experience,...
more
Multi-functional duct sensor for monitoring and control of heating, ventilation and air-conditioning systems
This bus capable and calibratable pressure measuring transducer enables the control of differential...
more
Good room climate is measurable! - AERASGARD® FSCO2 ⁄ FSTM-CO2 ⁄ FSFTM-CO2-Modbus
Our multifunctional room sensors for measuring temperature, humidity and CO2 concentration can now...
more
ISH | 11. - 15.03.2019 | Stand 10.3 A71
more