The maintenance-free microprocessor-controlled PREMASGARD® 232x - Modbus - T3 (series), with Modbus connection, impact-resistant plastic housing, housing cover with quick-locking screws, optionally with/ without display, is used for detecting positive, negative, or differential pressure measurement in clean air.
The piezo-resistive measuring element is temperature-compensated and guarantees high reliability and accuracy. The pressure transmitters are provided with a push-button for manual zero point calibration and an adjustable offset. Applications of these pressure sensors are in cleanroom, medical and filter technology, at ventilation and air conditioning ducts, at spray booths, in largescale catering facilities, for filter monitoring and level measurement, or for triggering frequency converters. Media measured with these pressure transducers are air (non-precipitating), or other gaseous non-aggressive, non-combustible media.
The pressure sensor has a manual zero point pushbutton. Fine adjustment by the user is possible at any time. The delivery includes the connection set ASD-06 (2 m connection hose, two pressure connection nipples, screws).
Voltage supply |
24 V AC (± 20 %) and 15…36 V DC |
---|---|
Power consumption | < 2 W/ 24 V DC, < 3.5 VA/ 24 V AC |
Measuring range, pressure | – 7000...+ 7000 Pa |
Media temperature | –20...+50 °C (temperature-compensated 0...+50 °C) |
Pressure connection |
4/ 6 x 11 mm (hoses Ø = 4/ 6 mm), metal pressure connection nozzles |
Type of pressure | differential pressure |
Accuracy, pressure |
(7000 Pa): typically ± 35 Pa at +25 °C compared to the calibrated reference device
|
Zero point offset | ± 10 % of final value |
Above- ⁄ below-pressure | max. ± 50 kPa |
Medium |
clean air and non-aggressive, non-combustible gases |
Electrical connection | 0.2 - 1.5 mm2, via push-in terminal |
Housing |
plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced, with quick-locking screws (slotted/ Phillips head - combination), colour traffic white (similar to RAL 9016), housing cover for display is transparent ! |
Housing dimensions | 108 x 78.5 x 45.8 mm (Tyr 3 with display) |
Cable gland |
2x M 20 x 1.5; with strain relief, exchangeable, inner diameter 8 - 13 mm |
Long-term stability | ± 1 %/ year |
Hysteresis | 0.3 % of final value |
Media contacting parts | Brass, Ni, Duroplast, Si, epoxy, RTV, BSG, UV silicone gel |
Temperature drift values | ± 0.1 %/ °C |
Linearity | < ± 1 % of final value |
Permissible air humidity | < 95 % r. H., non-precipitating air |
Protection class | III (according to EN 60 730) |
Protection type | IP 65 (according to EN 60 529) |
Standards |
CE conformity, electromagnetic compatibility according to EN 61326, according to EMC Directive 2014/ 30/ EU |
Optional |
two-line display with illumination, programmable, cutout approx. 36 x 15 mm (W x H), to display ACTUAL pressure or an individually programmable display value(The Modbus interface allows the display to beindividually configured in the 7-segment area andin the dot-matrix area.) |
sps smart production solutions – S+S Regeltechnik will be there 26. - 28.11.2019
Booth 8-219
Be our guest at Europe's leading trade fair for electric automation from 26 to...
more
THERMASGARD® TM65-Modbus -T3 - Calibratable immersion, screw-in or duct temperature measuring transducer
Patented high-quality product (patented immersion sensor, DE 10 2012 017 500.0) – basic device with...
more
PREMASGARD® 211x, 212x and 212x-SD - Compact and flexible specialists in pressure
These calibratable compact sensors from S+S can manage up to eight switchable measuring ranges from...
more