Efficient, convenient and network-enabled
Elegant appearance, touch-operated interface, large display, and Modbus-compatible
RYMaskon
The dew point control switch HYGRASREG® TW is installed on cooling or cold-water piping, or on cooled surfaces. It reliably detects formation of condensation by means of its humidity and temperature sensor (no conductivity measurement) and thanks to its patented measuring method, the pro-dynamic cross convention (Patent No. DE 10 2012 015 726.6), an exact measurement result, with ⁄ without optional display.
Dew point temperature is that temperature at which air reaches the state of saturation and water vapour starts to condensate. Facilitated by the measuring range of 0...100 % relative humidity of the TW-U and by the adjustable threshold value of 75...100 % relative humidity of the TW-W, it is possible for example to operate cooling ceilings so that the switching output of the dew point monitor, the DDC, is activated and then triggers a heater or other control elements thereby preventing the formation of dew before dew builds up on pipes or cooling ceilings of the property to be monitored.
Power consumption | < 1.1 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC |
---|---|
Sensors |
digital humidity sensor
with integrated temperature sensor, low hysteresis, high long-term stability |
Output signal | potential-free changeover contact (24 V), 1 A ohmic load |
Sensor protection | membrane filter |
Measuring range |
formation of dew is detected at 75...100 % r.H. on the TW-W, switching (switchpoint adjustable by potentiometer, factory setting 75 % r.H.) |
Electrical connection | 0.14 - 1.5 mm² via terminal screws |
Enclosure |
plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced, with quick-locking screws (slotted ⁄ Phillips head - combination), colour traffic white (similar to RAL 9016), enclosure cover for display is transparent ! |
Enclosure dimensions | 72 x 64 x 43.3 mm (Tyr 1 with Display) |
Cable gland |
2x M 12 x 1.5 (Y-adapter); with strain relief, exchangeable, max. inner diameter 6 mm |
Installation |
TW with strap for direct mounting on pipes or for direct mounting on flat surfaces (e.g. walls, ceilings) TW - external with detached sensor head (cable length KL = 1.5 m) for mounting on pipes |
Protection class | III (according to EN 60 730) |
Protection type | IP 65 (according to EN 60 529) |
Standards |
CE conformity, electromagnetic compatibility according to EN 61326, according to EMC Directive 2014 ⁄ 30 ⁄ EU |
Function |
The relay output is triggered (contact 13 -11 closed) if the pre-set switchpoint (factory setting 75 % r.H.) is not reached and opens (contact 12 -11 closed) in the event of an error (power failure, condensation). LED short pulses = LED long pulses = |
ISH Messe Frankfurt – S+S Regeltechnik looks forward to meeting you!
11. - 15.03.2019
Stand 10.3 A71
At the ISH, the world's leading trade fair for "The Bathroom Experience,...
more
Multi-functional duct sensor for monitoring and control of heating, ventilation and air-conditioning systems
This bus capable and calibratable pressure measuring transducer enables the control of differential...
more
Good room climate is measurable! - AERASGARD® FSCO2 ⁄ FSTM-CO2 ⁄ FSFTM-CO2-Modbus
Our multifunctional room sensors for measuring temperature, humidity and CO2 concentration can now...
more
ISH | 11. - 15.03.2019 | Stand 10.3 A71
more