TW-W EXTERN

HYGRASREG® TW-W EXTERN

Item No. 1202-1015-0021-030
EAN 4 251325 611587

The dew point control switch HYGRASREG® TW is installed on cooling or cold-water piping, or on cooled surfaces. It reliably detects formation of condensation by means of its humidity and temperature sensor (no conductivity measurement) and thanks to its patented measuring method, the pro-dynamic cross convention (Patent No. DE 10 2012 015 726.6), an exact measurement result, with ⁄ without optional display.

Dew point temperature is that temperature at which air reaches the state of saturation and water vapour starts to condensate. Facilitated by the measuring range of 0...100 % relative humidity of the TW-U and by the adjustable threshold value of 75...100 % relative humidity of the TW-W, it is possible for example to operate cooling ceilings so that the switching output of the dew point monitor, the DDC, is activated and then triggers a heater or other control elements thereby preventing the formation of dew before dew builds up on pipes or cooling ceilings of the property to be monitored.

137,70 € net
Power consumption < 1.1 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC
Sensors digital humidity sensor
with integrated temperature sensor,

low hysteresis, high long-term stability
Output signal potential-free changeover contact (24 V), 1 A ohmic load
Sensor protection membrane filter
Measuring range formation of dew is detected at
75...100 % r.H. on the TW-W, switching
(switchpoint adjustable by potentiometer,
factory setting 75 % r.H.)
Electrical connection 0.14 - 1.5 mm² via terminal screws
Enclosure plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted ⁄ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Enclosure dimensions 72 x 64 x 37,8 mm (Tyr 1)
Cable gland 2x M 12 x 1.5 (Y-adapter); with strain relief,
exchangeable, max. inner diameter 6 mm
Installation TW with strap for direct mounting on pipes
or for direct mounting on flat surfaces
(e.g. walls, ceilings)

TW - external with detached sensor head
(cable length KL = 1.5 m) for mounting on pipes

Protection class III (according to EN 60 730)
Protection type IP 65 (according to EN 60 529)
Standards CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014 ⁄ 30 ⁄ EU
Function The relay output is triggered (contact 13 -11 closed)
if the pre-set switchpoint (factory setting 75 % r.H.)
is not reached and opens (contact 12 -11 closed)
in the event of an error (power failure, condensation).

LED short pulses =
relay active → switchpoint not reached
ACTUAL humidity < pre-set switchpoint (no condensation)

LED long pulses =
relay inactive → switchpoint exceeded
ACTUAL humidity > pre-set switchpoint (condensation)

S+S Regeltechnik - Benefits to the power of five

Learn more

S+S Regeltechnik News

Exhibition Newsshow all

 

ISH Messe Frankfurt – S+S Regeltechnik looks forward to meeting you!
10. - 15.03.2019

Stand 10.3 A71
At the ISH, the world's leading trade fair for "The Bathroom Experience,...
more

Overview of all exhibition dates

Product Newsshow all

 

Multi-functional duct sensor for monitoring and control of heating, ventilation and air-conditioning systems

This bus capable and calibratable pressure measuring transducer enables the control of differential...
more

 

Good room climate is measurable! - AERASGARD® FSCO2 ⁄ FSTM-CO2 ⁄ FSFTM-CO2-Modbus

Our multifunctional room sensors for measuring temperature, humidity and CO2 concentration can now...
more

Exhibition News

ISH | 10. - 15.03.2019 | Stand 10.3 A71

more

Newsletter Subscription

Stay always informed about our products and news from S+S Regeltechnik