- New
- Sale
- Temperature
- Humidity
- Pressure
- Light Intensity & Motion
- Air Quality
- Flow
- Modbus | Wireless Modbus
- Room controller
- EtherCAT P
- Accessory
Description
Duct/ smoke gas temperature measuring transducer
THERMASGARD® RGTM 1
Calibratable THERMASGARD® RGTM 1 flue gas measuring transducer with eight switchable measuring ranges, exchangeable spring-mounted measuring insert, straight protective tube, connecting head made of aluminium, metal mounting flange and continuous output for the detection of high temperatures in gaseous media, e.g. for exhaust air or flue gas temperature measuring.
The sensor device is are factory-calibrated. Adjustment/Fine-tuning by the user is possible (range and zero-point are adjustable).
Technical details
Power consumption
< 1.0 VA/ 24 V AC/ DC; < 0.55 VA/ 24 V DC
Measuring range, temperature
– 20...+ 150 / 0... + 50 °C /+ 100 °C /+ 200 °C /+ 300 °C /+ 400 °C /+ 500 °C /+ 600 °C
Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance
máx. 750 Ohm/ 24 V DC
Sensor
Pt1000, DIN EN 60751, class B,
glass sensing resistor
(Perfect Sensor Protection)
glass sensing resistor
(Perfect Sensor Protection)
Connection type
2- or 3-wire connection
Accuracy
typically ± 0.2 K at +25 °C
Ambient temperature
Measuring transducer –30...+70 °C
Process connection
by mounting flange, stainless steel V2A (1.4305)
(included in the scope of delivery)
(included in the scope of delivery)
Protective tube
stainless steel, 1.4571, V4A, Ø = 8 mm
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Connecting head
form B, material aluminium,
colour white aluminium (similar to RAL 9006),
M 20 x 1.5
colour white aluminium (similar to RAL 9006),
M 20 x 1.5
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Output
4...20 mA
Measuring ranges
multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
with manual zero point correction (± 10 K)
see table (other ranges optional)
with manual zero point correction (± 10 K)
Protection type
IP 65 (according to EN 60 529)*
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
electromagnetic compatibility according to EN 61326,